5-13
5.2 Group 1: Basic Parameter
01-00
Maximum Output Frequency
Factory setting 60.00/50.00
Settings
50.0~400.00Hz
1
This parameter determines the drive’s maximum output frequency.
01-01
Maximum Voltage Frequency (Base Frequency)
Factory setting 60.00/50.00
Settings
0.00~400.00
Hz
1
This parameter must be set to the motor’s nameplate frequency rating.
01-02
Maximum Output Voltage
Factory setting 440.0
Settings
0.0~510.0V
1
This parameter must be set to the motor’s nameplate voltage rating.
01-03
Upper Midpoint Output Frequency
Factory setting 0.50
Settings
0.00~400.00Hz
01-04
Upper Midpoint Output Voltage
Factory setting
10.0
Settings
0.0~510.0V
01-05
Lower Midpoint Output Frequency
Factory setting 0.50
Settings
0.00~400.00Hz
01-06
Lower Midpoint Output Voltage
Factory setting
10.0
Settings
0.0~510.0V
01-07
Minimum Output Frequency
Factory setting 0.00
Settings
0.00~400.00Hz
01-08
Minimum Output Voltage
Factory setting 0.0
Settings
0.0~510.0V
1
Setting of the V/F curve figure is usually based upon the motor’s allowable loading
characteristics. Pay special attention to the motor’s heat dissipation, dynamic balance,
and bearing lubricity, if the loading characteristics exceed the loading limit of the motor.
1
When setting the V/F curve, please follow this hierarchy for frequency:
01-01 01-03 01-05 01-07. There is no hierarchy for the voltage setting, but a high
voltage at low output frequencies may cause motor failure. At low frequencies, always
use the lowest voltage necessary for the application.