5-5
1
Pr. 00-07: This parameter allows the user to input their password and disable the
parameter lockout. An incorrect password may be entered 3 times and then a “Pcode”
will flash on the display, alerting the user the password is incorrect. The drive must be
powered off and then powered on again to clear the Pcode display.
1
Pr. 00-08: This parameter allows the user to input their password to lock out the
parameters from further changes.
To enter a password, the same password must be input twice within two minutes. To
verify the password was entered correctly, display the content of Pr. 00-08. If the
content is “1”, the password is entered. If the content is “0”, no password is entered.
1
To permanently disable the password. Enter the password in Pr. 00-07, then enter 0
into Pr. 00-08 twice within two minutes.
1
To re-activate the password, either enter an incorrect password into Pr. 00-07 or power
down and then re apply power to the AC drive.
00-09
Frequency and the Operation Method of IP06
Factory setting
0
Settings
Bit 0 0 Frequency via the up/down keys
0
1
Frequency command enabled after pressing the
data/prog key
2
0
1
Bit 1
0 IP06&RS485 frequency memorized
0
1 IP06&RS485 frequency not memorized
2
1
2
Bit 2 0 Up/down pin frequency memorized
0
1 Up/down pin frequency not memorized
2
2
4
Bit 3 0 FWD/REV direction memorized
0
1 FWD/REV direction not memorized
2
3
8
Bit
4
0
Parameter
memorized
0
1
Parameter
not
memorized
2
4
16
This parameter allows the user to define the IP06 function. It also allows the user to
determine if the drive retains the direction and speed command after power has been
removed.
1
Pr. 00-09 = Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 = xxxxx
1
Bit0 = This setting determines if it is necessary to press the PROG/DATA key first, to
enable the frequency/torque commands via up/down keys on the IP06.
Summary of Contents for S3000 Series
Page 8: ...2 5 DIMENTIONS 2 5...
Page 9: ...2 6 403 216...
Page 10: ...2 7...
Page 11: ...2 8 S3000 IP06...