5-48
06-08
Over-Torque Detection Time (oL2)
Factory setting
0.1
Settings
0.0-60.0 Second
1
These parameters define the current level and detection time for the Over Torque
Detection function.
1
The Over Torque Detection level is a percentage of the rated drive current. The factory
setting is 150% of the drives rated current.
1
The Over Torque Detection time is the length of time the drive may be in an over torque
condition.
5%
06-07, 06-10
06-08, 06-11
Current
Example: When the output current exceeds the over torque detection level (Pr.06-07) and
exceeds the over torque detection time (Pr.06-08), the drive will display oL2 on
the keypad and will follow the setting in Pr.06-06.
06-09
Over-Torque Detection Selection 2 (OL3)
Factory setting 0
Settings
0
Disable
1
over-torque detection during constant speed operation, continue to
operate after detection
2
over-torque detection during constant speed operation, stop
operation after detection.
3
over-torque detection during operation, continue operation after
detection.
4
over-torque detection during operation, stop operation after
detection.
06-10
Over-Torque Detection Level 2 (OL3)
Factory setting
150
Settings
10~250%
06-11
Over-Torque Detection Time 2
(OL3)
Factory setting
0.1
Settings
0.0~60.0
s