02-10
Digital Input Operation Direction
Factory setting 0
Settings
0~65535
Bit
0~7 1 High
active
1
This parameter determines the level of the input signal operation.
02-11
Multi-Function Output 1 RA, RB, RC (Relay 1)
Factory setting
0
02-12
Multi-Function Output 2 MRA, MRC (Relay 2)
Factory setting
0
02-13
Multi-Function Output 3 MO1
Factory setting
0
02-14
Multi-Function Output 4 MO2
Factory setting
0
Settings
0 to 72
Settings
Functions
Explanations
0
No
Function
1
AC Drive Running
There is an output from the AC drive
2
Operation Speed Attained 1 (both
directions)
3
Operation Speed Attained 2 (both
directions)
4
Pre-set speed attained 1 (both directions)
5
Pre-set speed attained 2 (forward only)
6
Pre-set speed attained 1 (both directions)
7
Pre-set speed attained 2 1forward
direction)
10
Zero speed
Drive output is below Min Frequency
11
Over-torque1oL2)
Please refer to 06-08
12
Base block 1Pause)
13
Drive ready for use
AC drive has no faults
14
Low voltage alarm 1LV)
Please refer to 06-00
15
Error indication
16
Drive operation mode
Output is on when the external terminals
have command and off if keypad or
RS485 have control.
17
PCO Run
18
PCO suspended
19
1
st
step of PCO completed