5-49
06-12
Over-Torque limit
Factory setting
150
Settings
0~250%
1
This parameter sets the over torque limit used during torque control, V/F control, and
Vector control. When using an analog input set for “Torque Limit”, this parameter will set
the actual limit. The value in this parameter is based on the AC drive output current in %.
06-13
Electronic Thermal Relay Selection (I
2
t)
Factory setting
2
Settings
0 Inverter/vector motor
1 Standard motor
2 Electronic thermal relay function disabled
1
This parameter selects the type electronic thermal relay function based on the motor
characteristics.
Inverter/vector motor = windings designed for AC drive output and low speeds with
high currents.
Standard motor = windings not designed for AC drives. Motor has a shaft mounted fan
which offers poor cooling at low speeds
06-14
Electronic Thermal Relay Time (I
2
t)
Factory setting
60
Settings
30~600
s
1
This parameter sets the time period for the Electronic Thermal Relay (I
2
t) function.
1
2
3
4
5
60Hz or more
50Hz
10Hz
5Hz
0
20 40
60
80 100 120 140 160 180 200
Operation
time(min)
Load
factor
(%)
1
The electronic thermal relay function is designed to protect the motor from overheating,
due to low output frequency and high currents.
06-15
Heat Sink Over-Heat (oH) Warning
Factory setting
85.0
Settings
0.0~110.0
Unit
1
The setting for parameters 02-10~02-13 is 23.
*