5-63
Settings
Function
Settings
Function
3
7, O, 1 for ASCII
12
8, N, 1 for RTU
4
7, E, 2 for ASCII
13
8, N, 2 for RTU
5
7, O, 2 for ASCII
14
8, E, 1 for RTU
6
8, N, 1 for ASCII
15
8, O, 1 for RTU
7
8, N, 2 for ASCII
16
8, E, 2 for RTU
8
8, E, 1 for ASCII
17
8, O, 2 for RTU
1
Computer-controlled Link: when the RS-485 series connection communication interface
is utilized, every S3000 has to pre-determine the communication address at Pr. 09-00,
and thereafter, the computer will proceed with the control based on respective
addresses.
1
The Communication Protocol is of the MODBUS ASCII (American Standard Code for
Information Interchange) Mode: every byte is composed of 2 ASCII words. For
example, if the numeric value is 64 Hex, the way to show it through the ASCII mode will
be ”64”, which is composed respectively be ”6” (36Hex) and
”4” (34Hex).
1. Meaning of Encoding:
The communication protocol is of the Hexadecimal system, and thus, the meaning of the
ASCII message words would be: ”0”…”9”, ”A”…”F”, which every Hexadecimal code
represents every ASCII message word.
For instance:
WORD
‘0’
‘1’
‘2’
‘3’
‘4’
‘5’
‘6’
‘7’
ASCII
code
30H
31H
32H
33H
34H
35H
36H
37H
WORD
‘8’
‘9’
‘A’
‘B’
‘C’
‘D’
‘E’
‘F’
ASCII
code
38H
39H
41H
42H
43H
44H
45H
46H
2. WORD Structure
2.1 10-bit Word Frame (For ASCll)