5-32
03-13
Analog Input Noise Filter
Factory setting 0.10
Settings
0.00~2.00 s
1
Interferences commonly exist with analog signals, such as those entering AVI, ACI and AUI.
These interferences constantly affect the stability of analog control and using the Input
Noise Filter will create a more stable system.
1
If Pr. 03-13 is large, the control will be stable, yet the response to the input will be slow. If
Pr. 03-13 is small, the control may be unstable, yet the response to the input will fast.
03-14
Loss of the ACI signal
Factory setting 0
Settings
0
disabled
1 continue operation at last known frequency
2 decelerate to a stop
3 stop immediately and display E.F.
1
This parameter determines the operation of the drive when the 4~20mA (ACI) signal is lost.
03-15
Analog Output Selection
Factory setting 0
Settings
0-24
Full List of the Functions
Settings
Functions
Explanations
0
Output frequency
01-00=100%
1
Command frequency
01-00=100%
2
Speed
01-00=100%
3
Current
rated current of the inverter =100%
4
Output voltage
200V (400V) =100%
5
DC BUS voltage
400V (800V) =100%
6
Power factor
-1.000~1.000=100%
7
Power
rated power of the inverter =100%
8
Torque
full-load torque =100%
9
AVI
(0~10V=0~100%)
10
ACI
(0~20mA=0~100%)
11
AUI
(-10~10V=0~100%)
12
Torque current command
rated current of the inverter =100%
13
Torque current estimation
rated current of the inverter =100%
14
Exciting magnet current
command
rated current of the inverter =100%
15
Magnetic flux current
rated current of the inverter =100%