4-27
Group 8: High-Performance Parameter
Parameters
Functions
Settings
Factory
Setting
Customer
08-00
PID Feedback Terminal
Selection
0: Disable
1: AVI (0~10V)
2: ACI (4~20mA)
3: AUI ( +/-10V)
4: Clock (F/R--master speed)
5: Clock (F/R--A/B direction)
0
08-01
Proportional Gain (P)
0.0~500.0%
80.0
0.00~100.00 s
08-02
Integral
Time
(I)
0.00: no integral
1.00
08-03
Differential
Time
(D)
0.00~1.00 s
0.00
08-04
Integration’s Upper
Bound Frequency
0.0~100.0%
100.0
08-05
PID Frequency Output
Command limit
0.0~100.0%
100.0
08-06
PID Deviation Range
-100.0~+100.0%
0.0
08-07
One-Time
Delay
0.000~0.005 s
0.000
08-08
Detection Time of the
Feedback Error
0.0~6000.0 s
0.0
08-09
Feedback Signal Fault
Treatment
0: warn and keep operating
1: warn and RAMP to stop
2: warn and COAST to stop
0
08-10
Dwell (sleep)
Frequency
0.00~400.00Hz
0.00
08-11
Revival
Frequency
0.00~400.00Hz
0.00
08-12
Dwell (sleep) Period
0.0~6000.0 s
0.0
08-13
Fan control
0: when power is applied, the fan
will turn on
1:When the run command is
given, the fan will turn on
0