5-75
1
This parameter determines the PG feedback filter time for the AC drive to process the
motor’s rotation speed.
10-05
PG Slip Range
Factory setting
10.0
Settings
0.0~50.0%
1
This parameter determines the maximum slip range (deviation) for the PG feedback signal.
1
The slip range is calculated as follows (Pr. 10-05 x Pr. 01-00 = slip frequency). The slip
frequency value is than added to and subtracted from the “command frequency” to give a
“slip range”. If the encoder feedback gives a value outside this range, a PGerr will occur.
10-06
PG Stall Level (overspeed protection)
Factory setting
110.0
Settings
0.0~115.0%
1
This parameter determines the maximum PG feedback signal allowed before a fault will
occur.
1
The stall level is calculated as follows (Pr. 10-06 x Pr. 01-00 = maximum feedback
frequency). If the feedback signal is higher than this value, a PGerr will our.
10-07
PG Electrical Gear A
Factory setting
1
Settings
1~5000
10-08
PG Electrical Gear B
Factory setting
1
Settings
1~5000
1
These parameters are used when multiple feedback signals are used. One feedback
signal will trim the other. The actual output frequency will be based on the following
equation.
Output frequency = [PG frequency/PG point (Pr. 10-00)] * PG Electrical Gear A/ PG Electrical
Gear B.
10-09
PG Position Control Point (Home)
Factory setting
0
Settings
0~20000
10-10
Range for PG Position Attained (Home range)
Factory setting
10
Settings
0~20000