Chapter 2: Connecting External Equipment (Optional)
62
Mixing Diverse Sensor Types
You can mix DPX, DPX2, DPX3 and DX sensor packages on one BCM2
according to the following sensor combinations. In some scenarios, the
DPX3-ENVHUB4 sensor hub is required.
The BCM2 does NOT support any other sensor-mixing combinations than
those described in this section.
When mixing different sensor types, remember that the BCM2 supports
a maximum of 32 sensors/actuators.
1 DX + 1 DPX:
•
It is strongly recommended to use an RJ-12 to RJ-45 adapter to
connect the DPX sensor package to the DX sensor package.
Diverse combinations via the DPX3-ENVHUB4 sensor hub:
•
You must use the DPX3-ENVHUB4 sensor hub instead of the old
DPX-ENVHUB4 sensor hub. Each port on the hub supports any of the
following:
A DX sensor package
A chain of DX sensor packages
A DPX3 sensor package
A chain of DPX3 sensor packages
A DPX2 sensor package
A DPX sensor package
Summary of Contents for PMC-1000
Page 3: ...BCM2 Series Power Meter Xerus Firmware v3 4 0 User Guide...
Page 23: ...Chapter 1 Installation and Initial Configuration 11 Panel Wiring Example...
Page 54: ...Chapter 1 Installation and Initial Configuration 42 Branch Circuit Details...
Page 76: ...Chapter 2 Connecting External Equipment Optional 64...
Page 123: ...Chapter 3 Using the Web Interface 111...
Page 558: ...Appendix D RADIUS Configuration Illustration 546 Note If your BCM2 uses PAP then select PAP...
Page 563: ...Appendix D RADIUS Configuration Illustration 551 14 The new attribute is added Click OK...
Page 564: ...Appendix D RADIUS Configuration Illustration 552 15 Click Next to continue...
Page 594: ...Appendix E Additional BCM2 Information 582...
Page 612: ......