Chapter 2: Connecting External Equipment (Optional)
52
Supported Maximum DPX Sensor Distances
When connecting the following DPX sensor packages to the BCM2, you
must follow two restrictions.
•
DPX-CC2-TR
•
DPX-T1
•
DPX-T3H1
•
DPX-AF1
•
DPX-T1DP1
Sensor connection restrictions:
•
Connect a DPX sensor package to the BCM2 using the sensor cable
pre-installed (or provided) by Raritan. You MUST NOT extend or
modify the sensor cable's length by using any tool other than the
Raritan's sensor hubs.
•
If using a DPX-ENVHUB4 sensor hub, the cabling distance between
the BCM2 and the sensor hub is up to 33' (10 m).
Maximum distance illustration:
The following illustrates the maximum distance when connecting DPX
sensor packages with a maximum 16' (5 m) sensor cable to a BCM2 via a
sensor hub.
•
The sum of a DPX-T3H1 sensor cable's length is 16' (5 m).
•
The total cabling length between the BCM2 and one DPX-T3H1 is 49'
(15 m) as illustrated below.
Note that the length 16' (5 m) is the length of each DPX-T3H1 sensor
cable, which is defined in the above diagram.
BCM2
33' (10 m)
cable
1 sensor hub
16' (5 m)
cable
Up to 4 DPX-T3H1
sensor packages
Summary of Contents for PMC-1000
Page 3: ...BCM2 Series Power Meter Xerus Firmware v3 4 0 User Guide...
Page 23: ...Chapter 1 Installation and Initial Configuration 11 Panel Wiring Example...
Page 54: ...Chapter 1 Installation and Initial Configuration 42 Branch Circuit Details...
Page 76: ...Chapter 2 Connecting External Equipment Optional 64...
Page 123: ...Chapter 3 Using the Web Interface 111...
Page 558: ...Appendix D RADIUS Configuration Illustration 546 Note If your BCM2 uses PAP then select PAP...
Page 563: ...Appendix D RADIUS Configuration Illustration 551 14 The new attribute is added Click OK...
Page 564: ...Appendix D RADIUS Configuration Illustration 552 15 Click Next to continue...
Page 594: ...Appendix E Additional BCM2 Information 582...
Page 612: ......