Chapter 3: Using the Web Interface
189
•
To access the master device via SSH, the command is:
ssh -p 50200 192.168.84.77
Examples using standard TCP/UDP ports:
•
To access the master device via HTTPS, the IP address is:
https://192.168.84.77:443/
•
To access the master device via HTTP, the IP address is:
http://192.168.84.77:80/
•
To access the master device via SSH, the command is:
ssh -p 22 192.168.84.77
Slave 1 device:
Position code for Slave 1 is '01' so each port number is 5NN01 as shown
below.
Protocols
Port numbers
HTTPS
50001
HTTP
50101
SSH
50201
TELNET
50301
SNMP
50501
MODBUS
50601
Examples:
•
To access Slave 1 via HTTPS, the IP address is:
https://192.168.84.77:50001/
•
To access Slave 1 via HTTP, the IP address is:
http://192.168.84.77:50101/
•
To access Slave 1 via SSH, the command is:
ssh -p 50201 192.168.84.77
Slave 2 device:
Position code for Slave 2 is '02' so each port number is 5NN02 as shown
below.
Protocols
Port numbers
HTTPS
50002
HTTP
50102
Summary of Contents for PMC-1000
Page 3: ...BCM2 Series Power Meter Xerus Firmware v3 4 0 User Guide...
Page 23: ...Chapter 1 Installation and Initial Configuration 11 Panel Wiring Example...
Page 54: ...Chapter 1 Installation and Initial Configuration 42 Branch Circuit Details...
Page 76: ...Chapter 2 Connecting External Equipment Optional 64...
Page 123: ...Chapter 3 Using the Web Interface 111...
Page 558: ...Appendix D RADIUS Configuration Illustration 546 Note If your BCM2 uses PAP then select PAP...
Page 563: ...Appendix D RADIUS Configuration Illustration 551 14 The new attribute is added Click OK...
Page 564: ...Appendix D RADIUS Configuration Illustration 552 15 Click Next to continue...
Page 594: ...Appendix E Additional BCM2 Information 582...
Page 612: ......