3-34
Installing the Drive
AC890PX AC Drive
SET-UP PARAMETERS
PREF
6911Display
Default
Brief Description
V/Hz
SV
CLV
4-Q PMAC
27.03 MOTOR BASE
FREQUENCY
product code dependent Enter the motor nameplate
base frequency
x
x
x
27.04 MOTOR VOLTAGE product code dependent Enter the motor nameplate
voltage at base frequency
x
x
x
27.07 NAMEPLATE RPM
product code dependent Enter the motor nameplate
full-load rated speed. This
is the motor speed in rpm
at base frequency minus
full load slip.
x
x
x
27.09 MOTOR POLES
product code dependent
0 : 2 pole
1 : 4 pole
2 : 6 pole
3 : 8 pole
4 : 10 pole
5 : 12 pole
Enter the number of motor
poles from the motor
nameplate
x
x
x
27.08 MOTOR
CONNECTION
product code dependent
0 : DELTA
1 : STAR
Enter the type of motor
connection
x
x
71.01 PULSE ENC VOLTS
product code dependent Set between 10-20V to
match the encoder supply
voltage
x
71.02
ENCODER LINES
product code dependent
Set to the number of lines
used by the encoder
x