C-13
Certification
AC890PX AC Drive
EMC Immunity Levels
Port
Phenomenon
Basic standard
for test method
Level
Performance
(acceptance criterion)
Enclosure port
ESD
IEC 61000-4-2
4 kV CD or 8 kV AD
if CD impossible
B
Radio-frequency electromagnetic field, amplitude
modulated.
IEC 61000-4-3
see also 5.3.4
80 MHz to 1000 Mhz 10 V/m
80% AM (1 kHz)
A
Power ports
Fast transient-burst
IEC 61000-4-4
2 kV/5 kHz
a
B
Surge
b
1,2/50 µs, 8/20 µs
IEC 61000-4-5
1 kV
c
2 kV
d
B
Conducted radio-frequency common mode
e
IEC 61000-4-6
see also 5.3.4
0,15 MHz to 80 MHz
10 V
80 % AM (1 kHz)
A
Power interfaces
Fast transient-burst
e
IEC 61000-4-4
2 kV/5 kHz
Capacitive clamp
B
Signal interfaces
Fast transient-burst
e
IEC 61000-4-4
1 kV/5 kHz
Capacitive clamp
B
Conducted radio-frequency common mode
e
IEC 61000-4-6
see also 5.3.4
0,15 MHz to 80 MHz
10 V
80 % AM (1 kHz)
A
Ports for process
measurement
control lines
Fast transient-burst
e
IEC 61000-4-4
2 kV/5 kHz
Capacitive clamp
B
Surge
f
1,2/50 µs, 8/20 µs
IEC 61000-4-5
1 kV
d,f
B
Conducted radio-frequency common mode
e
IEC 61000-4-6
see also 5.3.4
0,15 MHz to 80 MHz
10 V
80 % AM (1 kHz)
A
CD : contact discharge
AD : air discharge AM : amplitude modulation
a
Power ports with current rating < 100 A: direct coupling using the coupling and decoupling network. Power ports with current rating ≥ 100 A: direct coupling
or capacitive clamp without decoupling network. If the capacitive clamp is used, the test level shall be 4 kV/2,5 kHz.
b
Applicable only to power ports with current consumption , 63 A during light load test conditions as specified in 5.1.3. The rated impulse voltage of the basic
insulation shall not be exceeded (see IEC 60664-1).
c
Coupling line-to-line.
d
Coupling line-to-earth.
e
Applicable only to ports or interfaces with cables whose total length according to the manufacturer's functional specification may exceed 3 m.
f
Applicable only to ports with cables whose total length according to the manufacturer's functional specification may exceed 30 m. In the case of a shielded
cable, a direct coupling to the shield is applied. This immunity requirement does not apply to fieldbus or other signal interfaces where the use of surge
protection devices is not practical for technical reasons. The test is not required where normal functioning cannot be achieved because of the impact of the
coupling/decoupling network on the equipment under test (EUT).
Minimum immunity requirements for PDSs intended for use in the second environment
Summary of Contents for AC890PX Series
Page 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Page 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Page 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Page 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Page 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...