B-9
Sequencing Logic
AC890PX AC Drive
Enable Operation
ANDed with the DRIVE ENABLE parameter on the SEQUENCING LOGIC function block.
When both Set (=1) is the same as:
DRIVE ENABLE
=
TRUE
When either or both Cleared (= 0) is the same as :
DRIVE ENABLE
=
FALSE
Enable Ramp Output, Enable Ramp, Enable Ramp Input
Not implemented. The state of these bits must be set (=1) to allow this feature to be added in the future.
Reset Fault
Replaces the REM TRIP RESET parameter on the SEQUENCING LOCIC function block. When Set (=1) is the same as:
REM TRIP RESET
=
TRUE
When Cleared (= 0) is the same as :
REM TRIP RESET
=
FALSE
Remote
Not implemented. It is intended to allow the PLC to toggle between local and remote. The state of this must be set (=1) to
allow this feature to be added in the future.
Example Commands
047F hexadecimal to RUN
047E hexadecimal to STOP