Programming
D-182
AC890PX AC Drive
Parameter Descriptions
JERK 1 to JERK 4
PREF: 118.04, 118.05,
118.06, 118.07
Default: 10.00 /s²
Range: 0.00 to 100.00 /s
3
Rate of change of acceleration for the relevant segment of the curve, i.e. JERK 1 is for segment 1, etc.
CONTINUOUS
PREF: 118.08
Default: FALSE
Range: FALSE / TRUE
When TRUE, it forces a smooth transition if the speed point is changed when ramping. The curve is controlled by the
ACCELERATION and JERK 1 to JERK 4 parameters. When FALSE, there is an immediate transition from the old curve to
the new curve.
HOLD
PREF: 118.09
Default: FALSE
Range: FALSE / TRUE
When TRUE, the output of the ramp is held at its last value.
SYMMETRIC JERK
PREF: 118.10
Default: FALSE
Range: FALSE / TRUE
When TRUE, JERK 1 is used for all segments of the curve. JERK 2, JERK 3 and JERK 4 are ignored.
RESET
PREF: 118.11
Default: FALSE
Range: FALSE / TRUE
If TRUE, the output is made equal to the input.
OFFSET
PREF: 118.12
Default: 0.0000 deg
Range: 0.0000 to 360.0000
deg
This input provides an additional offset to be applied to the Position Output
MAX SPEED
PREF: 118.18
Default: 1500.0 rpm
Range: 100.0 to 6000.0 rpm
This parameter specifies the maximum speed of the Virtual Master
SPEED FILT TIME
PREF: 118.22
Default: 5.0 ms
Range: 0.00 to 100.0 ms
When SOURCE is set to FEEDBACK POSN or REFERENCE ENCODR, the speed if filtered by the value set by this
parameter.
ACCEL FILT TIME
PREF: 118.23
Default: 5.0 ms
Range: 0.00 to 100.0 ms
When SOURCE is set to FEEDBACK POSN or REFERENCE ENCODR, the acceleration is filtered by the value set by this
parameter.
Summary of Contents for AC890PX Series
Page 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Page 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Page 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Page 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Page 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...