![Parker AC890PX Series Product Manual Download Page 56](http://html1.mh-extra.com/html/parker/ac890px-series/ac890px-series_product-manual_755704056.webp)
Installing the Drive
3-35
AC890PX AC Drive
SET-UP PARAMETERS
PREF
6911Display
Default
Brief Description
V/Hz
SV
CLV
4-Q PMAC
71.03 ENCODER INVERT
0 : FALSE
1 : TRUE
Rotating Autotune sets
actual value
Encoder direction :- when
TRUE, changes the sign of
the measured speed and
the direction of the position
count.
x
80.01 AUTOTUNE
ENABLE
0 : FALSE
1 : TRUE
Set TRUE to enable
Autotune. Resets to FALSE
when complete.
x
80.02 AUTOTUNE MODE
0 : ROTATING
1 : STATIONARY
2 : SPD LOOP
ROTATING
3 : SPD LOOP
STATIONARY
Set the type of Autotune.
x
x
27.06 MAG CURRENT
product code dependent
Rotating Autotune sets
actual value
Enter the No-Load Amps
from the motor nameplate
x
x
x
27.14 STATOR RES
product code dependent
Autotune sets actual
value
Motor per-phase stator
resistance
x
x
27.15 LEAKAGE INDUC
product code dependent
Autotune sets actual
value
Motor per-phase stator
leakage inductance
x
x
27.16 MUTUAL INDUC
product code dependent
Autotune sets actual
value
Motor per-phase stator
mutual (magnetising)
inductance
x
x
Summary of Contents for AC890PX Series
Page 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Page 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Page 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Page 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Page 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...