Programming
D-230
AC890PX AC Drive
2
PREF
Name
Block
Type
Range
Default
ro\rw
Notes
101.10 SPEED SETPOINT
REFERENCE
REAL
_.xx
0.00 %
ro
Output
101.11 REVERSE
REFERENCE
BOOL
0 : FALSE
1 : TRUE
FALSE
ro
Output
101.12 LOCAL SETPOINT
REFERENCE
REAL
_.xx
0.00 %
ro
Output
101.13 LOCAL REVERSE
REFERENCE
BOOL
0 : FALSE
1 : TRUE
FALSE
ro
Output
101.15 FWIRE SETPOINT
REFERENCE
REAL
_.xx
0.00 %
ro
Output
101.16 SPEED DEMAND
REFERENCE
REAL
_.x
0.0 Hz
ro
Output
102.01 RUN STOP MODE
REFERENCE STOP ENUM
0 : RUN RAMP
1 : COAST
2 : DC INJECTION
3 : STOP RAMP
RUN RAMP
rw
102.02 STOP TIME
REFERENCE STOP REAL
0.0 to 600.0 s
10.0 s
rw
102.03 STOP ZERO SPEED REFERENCE STOP REAL
0.00 to 100.00 %
0.10 %
rw
102.04 STOP DELAY
REFERENCE STOP REAL
0.000 to 30.000 s
0.500 s
rw
102.05 FAST STOP MODE
REFERENCE STOP ENUM
0 : RAMP
1 : COAST
RAMP
rw
102.06 FAST STOP LIMIT
REFERENCE STOP REAL
0.0 to 3000.0 s
30.0 s
rw
102.07 FAST STOP TIME
REFERENCE STOP REAL
0.0 to 600.0 s
0.1 s
rw
102.08 FINAL STOP RATE
REFERENCE STOP REAL
1 to 4800 Hz/s
1200 Hz/s
rw
103.01 SETPOINT
REFERENCE JOG
REAL
-100.00 to 100.00 %
10.00 %
rw
103.02 ACCEL TIME
REFERENCE JOG
REAL
0.0 to 3000.0 s
1.0 s
rw
103.03 DECEL TIME
REFERENCE JOG
REAL
0.0 to 3000.0 s
1.0 s
rw
105.01 STALL TIME
STALL TRIP
REAL
0.1 to 3000.0 s
480.0 s
rw
3
105.03 STALL LIMIT TYPE
STALL TRIP
ENUM
0 : TORQUE
1 : CURRENT
2 : TRQ OR CURRENT
TRQ OR CURRENT
rw
Summary of Contents for AC890PX Series
Page 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Page 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Page 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Page 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Page 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...