Programming
D-144
AC890PX AC Drive
SKIP FREQUENCIES
SETUP::MOTOR CONTROL::SKIP FREQUENCIES
This function block may be used to prevent the Drive operating at frequencies that cause mechanical resonance in the load.
Parameter Descriptions
INPUT
PREF: 91.01
Default: 0.00 %
Range: -300.00 to 300.00 %
The value of the block input in %.
BAND 1
PREF: 91.02
Default: 0.0 Hz
Range: 0.0 to 500.0 Hz
The width of each skip band in Hz.
FREQUENCY 1
PREF: 91.03
Default: 0.0 Hz
Range: 0.0 to 500.0 Hz
This parameter contains the centre frequency of each skip band in Hz.
BAND 2
PREF: 91.04
Default: 0.0 Hz
Range: 0.0 to 500.0 Hz
The width of each skip band in Hz.
FREQUENCY 2
PREF: 91.05
Default: 0.0 Hz
Range: 0.0 to 500.0 Hz
This parameter contains the centre frequency of each skip band in Hz.
BAND 3
PREF: 91.06
Default: 0.0 Hz
Range: 0.0 to 500.0 Hz
The width of each skip band in Hz.
FREQUENCY 3
PREF: 91.07
Default: 0.0 Hz
Range: 0.0 to 500.0 Hz
This parameter contains the centre frequency of each skip band in Hz.
BAND 4
PREF: 91.08
Default: 0.0 Hz
Range: 0.0 to 500.0 Hz
The width of each skip band in Hz.
FREQUENCY 4
PREF: 91.09
Default: 0.0 Hz
Range: 0.0 to 500.0 Hz
This parameter contains the centre frequency of each skip band in Hz.
Summary of Contents for AC890PX Series
Page 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Page 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Page 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Page 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Page 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...