Programming
D-186
AC890PX AC Drive
ZERO SPEED
SETUP::MOTOR CONTROL::ZERO SPEED
This function block detects when the motor speed is at or close to zero. HYSTERESIS and THRESHOLD are user-definable.
Parameter Descriptions
HYSTERISIS
PREF: 85.01
Default: 0.10 %
Range: 0.00 to 300.00 %
Provides a hysteresis band about which the outputs are stable.
IF the hysteresis value is >= to the Threshold
THEN the level is set to 2 x the hysteresis value and the Off level is set to zero,
ELSE the On level = Thr Hysteresis and the Off level = Threshold - Hysteresis.
THRESHOLD
PREF: 85.02
Default: 0.50 %
Range: 0.00 to 300.00 %
The nominal level below which the outputs are set.
AT ZERO SPD FBK
PREF: 85.03
Default: TRUE
Range: FALSE / TRUE
Speed feedback. TRUE when at zero speed feedback, as defined by THRESHOLD and HYSTERESIS.
IF (abs(speed feedback)) > On Level at zero speed = FALSE
ELSE if (abs(speed feedback)) <= Off Level at zero speed = TRUE
ELSE at zero speed is unchanged
AT ZERO SPD DMD
PREF: 85.04
Default: TRUE
Range: FALSE / TRUE
Speed demand. TRUE when at zero speed demand, as defined by THRESHOLD and HYSTERESIS.
AT STANDSTILL
PREF: 85.05
Default: TRUE
Range: FALSE / TRUE
TRUE when both AT ZERO SPD FBK and AT ZERO SPD DMD are TRUE.
Summary of Contents for AC890PX Series
Page 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Page 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Page 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Page 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Page 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...