D-233
Programming
AC890PX AC Drive
2
PREF
Name
Block
Type
Range
Default
ro\rw
Notes
112.03 CONTROL BAND
POWER LOSS
CNTRL
REAL
0 to 1000 V
20 V
rw
112.04 ACCEL TIME
POWER LOSS
CNTRL
REAL
0.01 to 300.00 s
10.00 s
rw
112.05 DECEL TIME
POWER LOSS
CNTRL
REAL
0.01 to 300.00 s
5.00 s
rw
112.06 TIME LIMIT
POWER LOSS
CNTRL
REAL
0.00 to 300.00 s
30.00 s
rw
112.07 PWR LOSS ACTIVE
POWER LOSS
CNTRL
BOOL
0 : FALSE
1 : TRUE
FALSE
ro
Output
112.08 INITIAL STEP
POWER LOSS
CNTRL
REAL
0.00 to 100.00 %
0.00 %
rw
113.01 RESET
ENERGY METER
BOOL
0 : FALSE
1 : TRUE
FALSE
rw
113.02 POWER
ENERGY METER
REAL
_.xx
0.00 kW
ro
Output
113.03 POWER
ENERGY METER
REAL
_.xx
0.00 hp
ro
Output
113.04 REACTIVE POWER
ENERGY METER
REAL
_.xx
0.00 kVAR
ro
Output
113.05 ENERGY USED
ENERGY METER
REAL
_.x
0.0 kW hr
ro
Output
113.07 POWER FACTOR
ENERGY METER
REAL
_.x
1.0
ro
Output
113.08 PF ANGLE
ENERGY METER
REAL
_.xx
0.00 deg
ro
Output
113.09 RAW POWER
ENERGY METER
REAL
_.xx
0.00 kW
ro
Output
113.10 RAW R. POWER
ENERGY METER
REAL
_.xx
0.00 kVAR
ro
Output
114.01 PRECHARGE
CLOSED
REGEN CNTRL
BOOL
0 : FALSE
1 : TRUE
TRUE
rw
114.02 DC VOLTS DEMAND
REGEN CNTRL
REAL
0 to 1200 V
720 V
rw
114.07 Id DEMAND
REGEN CNTRL
REAL
-1.5 to 1.5
0.1
rw
114.08 CURRENT
CONTROL
REGEN CNTRL
BOOL
0 : FALSE
1 : TRUE
FALSE
rw
Summary of Contents for AC890PX Series
Page 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Page 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Page 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Page 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Page 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...