![Parker AC890PX Series Product Manual Download Page 265](http://html1.mh-extra.com/html/parker/ac890px-series/ac890px-series_product-manual_755704265.webp)
D-25
Programming
AC890PX AC Drive
DRIVE CONFIG
SETUP::DRIVE SETUP::DRIVE CONFIG
This block contains general drive set-up parameters and also determines what hardware can be plugged in the A, B and F slots.
These parameters must be set correctly in order for the drive to run correctly.
Parameter Descriptions
DRIVE NAME
PREF: 136.01
Default: 890 DRIVE
Range:
Enter a user name for the drive.
CONTROL MODE
PREF: 136.02
Default: 0
Range: See below
This parameter defines how the drive will control the motor. If PMAC control is required, the motor wizard feature in the 890
DSE Configuration Tool
MUST
be used to correctly set-up the motor and feedback device parameters. Failure to do so may
result in damage to the servo motor.
Enumerated Value
:
CONTROL MODE
0 : VOLTS / Hz
1 : SENSORLESS VEC
2 : CLOSED-LOOP VEC
3 : 4-Q REGEN
4 : PMAC
Used to control Permanent-Magnet AC brushless motors.
SUPPLY VOLTAGE
PREF: 136.19
Default: 380V to 460V
Range
:
See below
Changes the dynamic braking threshold on expected supply voltage range.
Enumerated Value : Supply Voltage
0 : 230V
1 : 380V to 480V
2 : 500V
3 : 575V
4 : 690V
Summary of Contents for AC890PX Series
Page 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Page 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Page 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Page 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Page 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...