D-171
Programming
AC890PX AC Drive
TRIPS STATUS
SETUP::TRIPS::TRIPS STATUS
The Drive supports advanced and flexible trip logic to support monitoring of the Drive itself, the motor and the load. This
function block provides a view into the current trip condition(s) and allows some trips to be disabled.
Parameter Descriptions
DISABLED WORD 1
PREF: 97.01
Default: 0300
Range: 0x0000 to 0xFFFF
Use this parameter to disable trips. Not all trips may be disabled, the DISABLED WORD 1 mask is ignored for trips that
cannot be disabled. See below for which trips may be disabled and how this parameter is formed.
DISABLED WORD 2
PREF: 97.02
Default: 0840
Range: 0x0000 to 0xFFFF
Use this parameter to disable trips. Not all trips may be disabled, the DISABLED WORD 2 mask is ignored for trips that
cannot be disabled. See below for which trips may be disabled and how this parameter is formed.
DISABLED WORD 3
PREF: 97.10
Default: 0000
Range: 0x0000 to 0xFFFF
Use this parameter to disable trips. Not all trips may be disabled, the DISABLED WORD 3 mask is ignored for trips that
cannot be disabled. See below for which trips may be disabled and how this parameter is formed.
DISABLED WORD 4
PREF: 97.11
Default: 000
Range: 0x0000 to 0xFFFF
Use this parameter to disable trips. Not all trips may be disabled, the DISABLED WORD 4 mask is ignored for trips that
cannot be disabled. See below for which trips may be disabled and how this parameter is formed.
DISABLED WORD 5
PREF: 97.18
Default: 0000
Range: 0x0000 to 0xFFFF
Use this parameter to disable trips. Not all trips may be disabled, the DISABLED WORD 5 mask is ignored for trips that
cannot be disabled. See below for which trips may be disabled and how this parameter is formed.
DISABLED WORD 6
PREF: 97.19
Default: 0000
Range: 0x0000 to 0xFFFF
Use this parameter to disable trips. Not all trips may be disabled, the DISABLED WORD 6 mask is ignored for trips that
cannot be disabled. See below for which trips may be disabled and how this parameter is formed.
Summary of Contents for AC890PX Series
Page 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Page 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Page 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Page 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Page 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...