Installing the Drive
3-5
AC890PX AC Drive
Operating Conditions
Drive Enclosure Information
Operating Temperature
0
C to 40
C (32
F to 104
F), derate up to a maximum of 50
C
Derate linearly at 1% per degree centigrade for temperature exceeding the
maximum rating ambient for the drive.
Enclosure Rating
UL (c-UL) Enclosed Type 1 (North America/Canada) - as defined by UL50
CE - The enclosure meets the requirements of IP21 as defined by EN 60529
Enclosure Rating
The enclosure provides the following attenuation to radiated emissions:
EMC Enclosure Standard
Attenuation to RF in
spectrum 30-1000MHz
EN61800-3 Category C3
NONE
EN61800-3 Category C2 Restricted Distribution
EN61000-6-3
10db
EN61800-3 Category C1 Unrestricted Distribution
EN61000-6-4
20db
Humidity
Maximum 85% relative humidity at 40
C (104
F) non-condensing
Atmosphere
Non flammable, non corrosive and dust free
Altitude
If greater than 1000m above sea level, derate by 1% per 100m to a
maximum of 4600m
Safety:
Overvoltage Category
Overvoltage Category
III
Pollution Degree Pollution Degree
II
(non-conductive pollution, except for temporary
condensation)
Summary of Contents for AC890PX Series
Page 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Page 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Page 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Page 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Page 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...