Installing the Drive
AC890PX AC Drive
ANALOG I/O
Name
Range
Description
X12
01
0V
0V reference for analog I/O
02
AIN1
0-10V,
10V
Analog Input 1 (default = diff I/P +)
03
AIN2
0-10V,
10V
Analog Input 2 (default = diff I/P -)
04
AIN3
10V, 0-10V,
0-20mA, 4-20mA
Analog Input 3 (default = remote set point I/P)
-10V = 100.00% reverse, +10V = 100.00% forward (%
maximum speed)
05
AIN4
10V, 0-10V,
0-20mA, 4-20mA
Analog Input 4 (default = speed trim I/P)
06
AOUT1
10V
(10V = 100% speed)
Analog Output 1 (default = speed feedback O/P)
07
AOUT2
10V
(10V = 200% torque)
Analog Output 2 (default = torque feedback O/P)
08
+10V REF
+10V (output)
10V reference for analog i/o. Load 10mA maximum
09
–10V REF
-10V (output)
10V reference for analog i/o. Load 10mA maximum
NOTE
AIN1 and AIN2 are fitted with a link to ensure no noise pick-up when not in use. These terminals can be used together
as a differential
10V input (which we call AIN5), but AIN1 and AIN2 must remain within
10V relative to 0V. AIN5
has a direct input into the Speed Loop providing a fast speed or torque demand for servos.
All analog inputs/outputs are configurable using the DSE 890 (Drive System Explorer) Configuration Tool supplied on disk.
The table above shows the factory defaults. These analog connections require
10V DC which is supplied at terminal X12/08
and X12/09 respectively. For further information refer to the DSE 890 Configuration Tool.
Summary of Contents for AC890PX Series
Page 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Page 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Page 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Page 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Page 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...