This function block may be used to generate a trip or an alarm. The text for the trip message on the MMI may be customised.
Parameter Descriptions
CUSTOM ALARM 1 - 7
PREF: 165.01 to 165.07
Default: FALSE
Range: FALSE / TRUE
When TRUE, this causes an alarm message to appear on the display/keypad. This message may be cleared from the display by
pressing the E key. An alarm does not cause the drive to stop. The corresponding bit in the TRIPS STATUS::WARNINGS
WORD 5 parameter will be match this input.
CUSTOM TRIP 1 - 7
PREF: 165.08 to 165.14
Default: FALSE
Range: FALSE / TRUE
When TRUE this causes the drive to trip, which causes the drive to stop. The corresponding bit in the TRIPS
STATUS::ACTIVE WORD 5 parameter will remain TRUE until the trip is reset. Refer to the "Trips and Fault Finding"
chapter.
CUSTOM NAME 1 - 7
PREF: 165.15 to 165.21
Default: CUSTOM TRIP
Range: max length 16 chars
Text entered here will be shown on the 6901 display/keypad when the corresponding alarm or trip becomes active. If no text is
entered then the default trip text will be shown. Refer to the CUSTOM TRIPS 1-7 shown in the "Trips and Fault Finding"
chapter.
Summary of Contents for AC890PX Series
Page 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Page 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Page 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Page 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Page 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...