5-2
Associated Equipment
AC890PX AC Drive
Main Points
Connect the associated equipment in the following order:
890PX
motor
brake resistor
(noisy)
(noisy)
signal/control cable
(sensitive)
(noisy)
motor
cable
motor
choke
(noisy)
filter
motor
output
EMC
Overload
power
supply
(clean)
cable
890PX
EMC Motor Output Filter
This can help the drive achieve EMC and filter thermal conformance. It also ensures longer motor life by reducing the high
voltage slew rate and overvoltage stresses. Mount the filter as close to the VSD as possible. Please refer to Parker Hannifin
Manufacturing for the selection of a suitable filter.
Motor Choke
Maximum Motor dv/dt = 10,000V/
s. This can be reduced (when cabling is over 50m in length - to a maximum of 300m) by
adding a motor choke in series with the motor.
Installations with long cable runs may suffer from nuisance overcurrent trips. A choke may be fitted in the drive output to
limit capacitive current. Screened cable has a higher capacitance and may cause problems in shorter runs. Contact Parker SSD
Drives for recommended choke values.
Summary of Contents for AC890PX Series
Page 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Page 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Page 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Page 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Page 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...