B-3
Sequencing Logic
AC890PX AC Drive
SEQUENCING LOGIC Function Block - State Outputs
The following table shows the states of individual parameters for the SEQUENCING LOGIC function block required to
produce the condition of the MAIN SEQ STATE parameter.
START
DISABLED
START
ENABLED
SWITCHED
ON
READY
ENABLED
F-STOP
ACTIVE
TRIP
ACTIVE
TRIPPED
Tripped
FALSE
FALSE
FALSE
FALSE
FALSE
FALSE
TRUE
TRUE
Running
FALSE
FALSE
FALSE
FALSE
TRUE
FALSE
FALSE
FALSE
Jogging
FALSE
FALSE
FALSE
FALSE
Note 1
FALSE
FALSE
FALSE
Stopping
FALSE
FALSE
FALSE
FALSE
Note 2
TRUE
FALSE
FALSE
Output
Contactor
Depends on
previous
state
Depends on
previous
state
TRUE
TRUE
TRUE
TRUE
TRUE
FALSE
Switch On
Enable
FALSE
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
FALSE
Switched On
FALSE
FALSE
TRUE
TRUE
TRUE
TRUE
TRUE
FALSE
Ready
FALSE
FALSE
FALSE
TRUE
TRUE
TRUE
TRUE
FALSE
Healthy
TRUE
TRUE
TRUE
TRUE
TRUE
TRUE
FALSE
FALSE
Note 3
Table B-2 Parameter States for the MAIN SEQ STATE Parameter
NOTE
1. JOGGING is set TRUE once the jog cycle has started, and remains TRUE until the jog cycle has finished which is
when either the stop delay has finished or another mode is demanded.
2. STOPPING is set TRUE during the stopping cycles commanded by either RUNNING going low, JOGGING going
low or if Fast Stop is active, i.e. SEQUENCING LOGIC is F-STOP ACTIVE.
3. Once Run and Jog are both FALSE, HEALTHY O/P will be set TRUE.
Summary of Contents for AC890PX Series
Page 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Page 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Page 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Page 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Page 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...