![Parker AC890PX Series Product Manual Download Page 123](http://html1.mh-extra.com/html/parker/ac890px-series/ac890px-series_product-manual_755704123.webp)
6-9
Operating the Drive
AC890PX AC Drive
SPEED DEMAND
REMOTE SETPOINT
Speed 0%
RUN input
Ramp to zero speed at
DECEL TIME
Ramp SPEED TRIM to
zero at STOP TIME
SPEED TRIM
POWER
CIRCUIT
DISABLED
STOP DELAY
Figure 3.4
Ramp to Stop with a Remote Reference
SPEED DEMAND
REMOTE SETPOINT
Speed 0%
RUN input
Ramp SPEED DEMAND
to zero at STOP TIME
SPEED TRIM
POWER
CIRCUIT
DISABLED
STOP DELAY
Figure 3.5
Remote to Stop with a Remote Reference: DECEL TIME = 0.0s
A special case exists when the DECEL TIME is set to 0.0 seconds, or when the HOLD parameter is TRUE. In both these
situations the SPEED DEMAND will ramp down to zero at the STOP TIME.