D-141
Programming
AC890PX AC Drive
Parameter Descriptions
TRIPPED
PREF: 92.13
Default: FALSE
Range: FALSE / TRUE
Indicates that there is a latched trip present.
RUNNING
PREF: 92.14
Default: FALSE
Range: FALSE / TRUE
Indicates that that the Drive is in the enabled state.
JOGGING
PREF: 92.15
Default: FALSE
Range: FALSE / TRUE
Indicates that the Drive is in the JOG mode.
STOPPING
PREF: 92.16
Default: FALSE
Range: FALSE / TRUE
Indicates that the Drive is stopping.
OUTPUT CONTACTOR
PREF: 92.17
Default: FALSE
Range: FALSE / TRUE
Output to be used to drive an external contactor in the motor output. This contactor is normally closed unless a Trip condition
has occurred or the Drive goes into the re-configuration mode.
SWITCH ON ENABLE
PREF: 92.18
Default: FALSE
Range: FALSE / TRUE
Sometimes referred to as READY TO SWITCH ON, this parameter indicates that the Drive will accept a run command.
SWITCHED ON
PREF: 92.19
Default: FALSE
Range: FALSE / TRUE
Run accepted. Waiting for CONTACTOR CLOSED and any motor deflux delay to be completed
READY
PREF: 92.20
Default: FALSE
Range: FALSE / TRUE
Indicates that the Drive’s power stack is operable and the Drive will run if enabled.
SYSTEM RESET
PREF: 92.21
Default: FALSE
Range: FALSE / TRUE
TRUE for a single block diagram execution cycle after the Drive enters either RUN or JOG mode.
Summary of Contents for AC890PX Series
Page 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Page 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Page 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Page 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Page 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...