Programming
D-210
AC890PX AC Drive
2
PREF
Name
Block
Type
Range
Default
ro\rw
Notes
65.07
LOW LIMIT
DISPLAY SCALE 1 REAL
-32768.0000 to
32767.0000
0.0000
rw
65.08
UNITS
DISPLAY SCALE 1 STRING max length is 6 chars
rw
66.01
DECIMAL PLACE
DISPLAY SCALE 2 ENUM
0 : DEFAULT
1 : X.XXXX
2 : X.XXX
3 : X.XX
4 : X.X
5 : X.
DEFAULT
rw
66.02
FORMULA
DISPLAY SCALE 2 ENUM
0 : A/B * X + C
1 : A/B * (X+C)
2 : A/(B * X) + C
3 : A/(B * (X+C))
A/B * X + C
rw
66.03
COEFFICIENT A
DISPLAY SCALE 2 REAL
-32768.0000 to
32767.0000
1.0000
rw
66.04
COEFFICIENT B
DISPLAY SCALE 2 REAL
-32768.0000 to
32767.0000
1.0000
rw
66.05
COEFFICIENT C
DISPLAY SCALE 2 REAL
-32768.0000 to
32767.0000
0.0000
rw
66.06
HIGH LIMIT
DISPLAY SCALE 2 REAL
-32768.0000 to
32767.0000
0.0000
rw
66.07
LOW LIMIT
DISPLAY SCALE 2 REAL
-32768.0000 to
32767.0000
0.0000
rw
66.08
UNITS
DISPLAY SCALE 2 STRING max length is 6 chars
rw
67.01
DECIMAL PLACE
DISPLAY SCALE 3 ENUM
0 : DEFAULT
1 : X.XXXX
2 : X.XXX
3 : X.XX
4 : X.X
5 : X.
DEFAULT
rw
Summary of Contents for AC890PX Series
Page 17: ...2 5 Product Overview AC890PX AC Drive 890PX bottom wire entry ...
Page 144: ...The Keypad 7 9 AC890PX AC Drive The Menu System Map ...
Page 145: ...7 10 The Keypad AC890PX AC Drive The Menu System Map continued ...
Page 328: ...Programming D 88 AC890PX AC Drive Functional Description ...
Page 386: ...Programming D 146 AC890PX AC Drive Setpoint Drive Frequency Frequency 1 Frequency 2 ...