5-52
5
1-1
1-4 : Single-phase model
1-2 : 3-phase model
3-1 : Single-phase model
2-1 : 3-phase model
Check for open circuit and the voltage at the breaker.
if a problem is found, fix it and check again.
Yes
No
Turn the power back on and check again.
Is the alarm triggered again?
1-4
2-1
Power wiring N-phase is connected.
Power wiring L2 and N are reverse connected. (3-phase only)
The connector CN-PRY2 on the outdoor CR PC board is
connected properly (locked). (3-phase only)
1-2
1-3
4-1
Yes
No
Correct wiring
1-3
Yes
No
Correct wiring
1-4
Yes
No
1 Check
the power
supply &
the wiring
Are the wires (RE1, RE2) from the reactor firmly installed?
3-1
3-2
Correct wiring
Yes
No
Turn the power back on and check again.
Is the alarm triggered again?
3-2
Replace the outdoor
unit HIC PC board.
4-1
Yes
No
3 Check the
outdoor
unit HIC
PC board
2 Check the
outdoor
unit CR
PC board
There may be a instantaneous blackout failure.
If there is nothing abnormal, see what happens.
4-1
4 Final check
P05 AC Power Supply Trouble
Error Detection Method
Error Diagnosis
Instantaneous blackout
•
Note : The work involved in diagnosing each of the items is extremely dangerous, so turn the power off at the breaker before
performing the tests.
Zero-cross (waveform input of power supply) error
•
DC voltage charge failure
•
1.
2.
Is the voltage on each of the
terminal boards 10%
of the rated voltage?
Correct wiring
(connector)
3-1
Yes
No
4hp
Common in RE1 and RE2
: Plug-in type
5hp, 6hp : Fastening screw type
*
3-phase outdoor unit HIC PC board
(for 3-phase outdoor unit CR PC board)
Single-phase outdoor unit HIC PC board
RE1*
RE2*
RE1
RE2
CN-PRY2
SM830211-07̲PAC-i.indb 52
SM830211-07̲PAC-i.indb 52
2013/09/07 10:42:30
2013/09/07 10:42:30
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...
Page 739: ...201309 ...