Single-Type
1-1. Unit Specifications
PE1
1. 4-Way Cassette Type S-50PU1E5 / U-50PE1E5
INDOOR
MODEL
S-50PU1E5
PANEL
MODEL
CZ-KPU2
-
OUTDOOR
MODEL
U-50PE1E5
Branch pipe
MODEL
-
PERFORMANCE TEST CONDITION
ISO5151 / EN14825
POWER SUPPLY
ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
C
O
O
L
I
N
G
CAPACITY
kW
5.0
5.0
5.0
BTU/h
17100
17100
17100
CURRENT
A
0.22
0.22
0.21
6.50
6.20
5.95
INPUT POWER
W
25
25
25
1.325k
1.325k
1.325k
TOTAL W
1.350k
1.350k
1.350k
ANNUAL CONSUMPTION TOTAL kWh 4
675
675
675
EER/EER CLASS
TOTAL(W/W) 5/("A"~"G")
3.70
3.70 / A
3.70
Min
1.5
5100
-
-
260
-
5.77
Max
5.6
19100
-
-
2.000k
-
2.80
Erp
6
Pdsign
kW
-
5.0
-
SEER
(W/W)
-
6.5
-
Annual consumption
kWh
-
269
-
Class
-
A++
-
POWER FACTOR
%
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
93
93
93
-
-
NOISE INDOOR
dB-A (H/M/L)
Power Level dB
32/29/27
49/46/44
NOISE OUTDOOR
dB-A (H/L)
Power Level dB
46/-
65/-
H
E
A
T
I
N
G
CAPACITY
kW
BTU/h
CURRENT
A
INPUT POWER
W
5.6
19100
0.20
25
5.6
19100
0.20
25
5.6
19100
0.19
25
TOTAL W
-
COP/COP CLASS
TOTAL(W/W) 5/("A"~"G")
-
-
-
1.5
5100
-
-
220
6.82
6.5
22200
-
-
2.300k
2.83
Erp
6
Pdsign
kW
-
-
-
Tbivalen
°C
-
-
-
SCOP
(W/W)
-
-
-
Annual consumption
kWh
-
-
-
Class
-
-
-
POWER FACTOR
%
-
-
-
6.90
1.405k
1.430k
3.92
-
-
-
-
-
93
6.60
1.405k
1.430k
3.92 / A
4.0
-10
3.8
1474
A
93
6.30
1.405k
1.430k
3.92
-
-
-
-
-
93
-
-
NOISE INDOOR
⁄
⁄
dB-A (H/M/L)
Power Level dB
NOISE OUTDOOR
⁄
⁄
dB-A (H/L)
Power Level dB
32/29/27
49/46/44
-
-
-
-
50/-
69/-
EXTRA LOW TEMP Total CAPACITY(kW)/INPUT POWER(W)/COP
-
MAX CURRENT(A)/MAX INPUT POWER(W)
0.22/25
⁄
-
0.22/25
-
0.21/25
-
12/2.46k
6.90/1.4k
12/2.57k
6.60/1.4k
12/2.68k
6.30/1.4k
⁄
-
-
STARTING CURRENT(A)/COMP OUTPUT(W)
NETWORK IMPEDANCE (ΩMAX.)
FM OUTPUT (W)
60
90
⁄
MOISTURE REMOVAL VOLUME
L/h(Pt/h)
2.8
(5.9)
-
External static pressure
Pa
-
I/D AIR
FLOW
COOL
m
3
/min (ft
3
/min)
16
(565)
HEAT
m
3
/min (ft
3
/min)
16
(565)
O/D AIR
FLOW
COOL
m
3
/min (ft
3
/min)
30
(1067)
HEAT
m
3
/min (ft
3
/min)
35
(1225)
REFRIGERANT TYPE, AMOUNT
g
(oz)
R410A
1.65k
(58.2)
/
P
R
O
D
I
M
HEIGHT : H mm(inch)
/
WIDTH : W mm(inch)
/
DEPTH : D mm(inch)
256 (10-3/32)
840 (33-3/32)
840 (33-3/32)
569 (22-13/32)
790 (31-7/64)
285 (11-7/32)
/
P
A
C
D
I
M
HEIGHT : H mm
/
WIDTH : W mm
/
DEPTH : D mm
298
929
929
645
921
386
/
MASS
(NET) k
g
(lb)
/
(GROSS) k
g
(lb)
23 (51)
29 (64)
42 (93)
46 (101)
/
LAYERS LIMIT (actually)
11 (12)
4 (5)
Operation
Condition
Cool (DBT)
18°C ~ 32°C
-15°C ~ 46°C
Heat (DBT)
16°C ~ 30°C
-20°C ~ 24°C
P
I
P
I
N
G
PIPE DIAMETER mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø6.35(1/4) (Gas)ø12.7(1/2)
CONNECT METHOD, STD LENGTH m (ft)
flared type, 5.0(16.4)
flared type, 5.0(16.4)
PIPE LENGTH RANGE m (ft)
5 ~ 40
(16.4 ~ 131.2)
~
~
I/D&O/D HEIGHT DIFFERENCE m (ft)
15 (OD located lower) / 30 (OD located higher)
(49.2/98.4)
ADD GAS AMOUNT
g
/m (oz/ft)
20
(0.215)
PIPE LENGTH FOR ADDITIONAL GAS m (ft)
30
(98.4)
*1
:
In case it is necessary to indicate the air flow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:
If the EUROVENT Certified models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230 V shall be used.
*3
:
Network Impedance shall be applicable for EUROPE and CHINA models.
*4
:
The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
:
EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:
SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season,
Other fiche data indicates in an attached sheet.
SM830211-07̲PAC-i.indb 6
SM830211-07̲PAC-i.indb 6
2013/09/17 22:44:41
2013/09/17 22:44:41
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...
Page 739: ...201309 ...