1-80
1
*1
:
In case it is necessary to indicate the air fl ow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:
If the EUROVENT Certifi ed models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230 V shall be used.
*3
:
Network Impedance shall be applicable for EUROPE and CHINA models.
*4
:
The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
:
EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:
SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season,
Other fiche data indicates in an attached sheet.
Single -Type
1-1. Unit Specifi cations
PE1
4. Ceiling Type S-140PT2E5 / U-140PE1E5
INDOOR
MODEL
S-140PT2E5
PANEL
MODEL
-
-
OUTDOOR
MODEL
U-140PE1E5
Branch pipe
MODEL
-
PERFORMANCE TEST CONDITION
ISO5151 / EN14825
POWER SUPPLY
ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
CAPACITY
kW
14.0
14.0
14.0
3.3
15.0
BTU/h
47800
47800
47800
11300
51200
CURRENT
A
0.94
0.91
0.88
21.2
20.5
19.8
-
-
INPUT POWER
W
120
120
120
4.530k
4.530k
4.530k
-
-
TOTAL W
-
4.650k
4.650k
4.650k
840
5.650k
ANNUAL CONSUMPTION TOTAL W 4
-
-
2325
-
-
-
EER/EER CLASS
TOTAL(W/W) 5/("A"~"G")
-
-
-
3.01
3.01 / B
3.01
3.93
2.65
Erp
6
Pdsign
kW
-
-
-
-
-
-
SEER
(W/W)
-
-
-
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
Class
-
-
-
-
-
-
POWER FACTOR
%
-
-
-
97
96
96
-
-
NOISE INDOOR
(H/M/L)
dB-A
47/41/37
Power Level dB
65/59/55
NOISE OUTDOOR
(H/L)
dB-A
54/-
Power Level dB
71/-
H
E
A
T
I
N
G
CAPACITY
kW
16.0
16.0
16.0
4.1
18.0
BTU/h
54600
54600
54600
14000
61400
CURRENT
A
0.94
0.91
0.88
19.8
19.2
18.5
-
-
INPUT POWER
W
120
120
120
4.240k
4.240k
4.240k
-
-
TOTAL W
-
4.360k
4.360k
4.360k
900
5.930k
COP/COP CLASS
TOTAL(W/W) 5/("A"~"G")
-
-
-
3.67
3.67 / A
3.67
4.56
3.04
Erp
6
Pdsign
kW
-
-
-
-
-
-
Tbivalen
°C
-
-
-
-
-
-
SCOP
(W/W)
-
-
-
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
Class
-
-
-
-
-
-
POWER FACTOR
%
-
-
-
97
96
95
-
-
NOISE INDOOR
(H/M/L)
dB-A
47/41/37
-
⁄
⁄
Power Level dB
65/59/55
-
NOISE OUTDOOR
(H/L)
dB-A
-
55/-
⁄
⁄
Power Level dB
-
71/-
EXTRA LOW TEMP Total CAPACITY(kW)/INPUT POWER(W)/COP
-
MAX CURRENT(A)/MAX INPUT POWER(W)
0.94/120
0.91/120
0.88/120
30.0/6.40k
30.0/6.62k
30.0/6.84k
⁄
STARTING CURRENT(A)/COMP OUTPUT(W)
-
-
-
21.1/2.0k
20.5/2.0k
19.8/2.0k
⁄
NETWORK IMPEDANCE (
Ω
MAX.)
-
-
FM OUTPUT (W)
111
90×2
⁄
MOISTURE REMOVAL VOLUME
L/h(Pt/h)
9.0
(18.9)
-
External static pressure
Pa
-
I/D AIR
FLOW
COOL
m
3
/min (ft
3
/min)
35
(1236)
HEAT
m
3
/min (ft
3
/min)
35
(1236)
O/D AIR
FLOW
COOL
m
3
/min (ft
3
/min)
135
(4767)
HEAT
m
3
/min (ft
3
/min)
120
(4238)
REFRIGERANT TYPE, AMOUNT
g
(oz)
R410A 3.40k
(119.9)
/
P
R
O
D
I
M
HEIGHT : H mm(inch)
235
9-1/4
1416
55-3/4
/
WIDTH : W mm(inch)
1590
62-19/32
940
37-1/32
/
DEPTH : D mm(inch)
690
27-5/32
340
13-13/32
/
P
A
C
D
I
M
HEIGHT : H mm
360
1556
/
WIDTH : W mm
1655
1055
/
DEPTH : D mm
820
485
/
MASS
(NET) k
g
(lb)
40
(88)
98
(216)
/
(GROSS) k
g
(lb)
49
(108)
108
(238)
/
LAYERS LIMIT (actually)
9 (10)
1 (2)
Operation
Condition
Cool O.D(DBT)
18°C ~ 32°C
-15°C ~ 46°C
Heat O.D(DBT)
16°C ~ 30°C
-20°C ~ 24°C
P
I
P
I
N
G
PIPE DIAMETER mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
CONNECT METHOD, STD LENGTH m (ft)
fl
ared type, 5.0(16.4)
fl
ared type, 5.0(16.4)
PIPE LENGTH RANGE m (ft)
5 ~ 75
(16.4 ~ 246.1)
~
~
I/D&O/D HEIGHT DIFFERENCE m (ft)
15 (OD located lower) / 30 (OD located higher)
(49.2/98.4)
ADD GAS AMOUNT
g
/m (oz/ft)
50
(0.538)
PIPE LENGTH FOR ADDITIONAL GAS m (ft)
30
(98.4)
SM830211-07̲PAC-i.indb 80
SM830211-07̲PAC-i.indb 80
2013/09/17 22:45:36
2013/09/17 22:45:36
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...
Page 739: ...201309 ...