4-13
4
4) Cooling High-Load Prevention Control
This system control is performed to limit the inverter frequency in order to restrict high pressure’s abnormal increase
and high-load operating prevention in the cooling mode.
In accordance with the temperature of the outdoor heat exchanger temperature sensors (C1, C2), such controls are
performed as to halting the operations of the indoor unit, decreasing the inverter frequency and restricting its increase,
etc.
When the maximum temperatures sensor (C1, C2) exceeds 64°C, operations of the indoor unit are halted and
restarted after 3 minutes.
If this start/stop activity is repeated 10 times, the alarm "P20" (cooling high-load error) occurs.
max. (C2, C1)
Outdoor unit operations halted
Frequency decreased
Frequency increases prevented
Frequency increased slower than normal
Normal operations (no control)
b
a
c
d
e
Control point
50PE
60PEY 71PEY
a
b
c
d
e
64
61
59
58
53
64
59
58
57
53
64
59
58
57
53
Control
point
a
b
c
50PE
65
54 (56)
52
60PEY
65
54 (56)
52
71PEY
65
54 (56)
52
°C
°C
max. (E1, E2)
a
b
c
5) Heating High-Load Prevention Control
This system control is performed to limit the inverter frequency in order to restrict high pressure’s abnormal increase
and high-load operating prevention in the heating mode.
In accordance with the temperature of the indoor heat exchanger temperatures sensor (E1, E2), such controls are
performed as to halting the operations of the indoor unit, decreasing the inverter frequency and restricting its increase,
etc.
When the maximum temperatures sensor (E1, E2) exceeds 65°C, the outdoor unit operation is halted and restarted
after 3 minutes.
Outdoor unit operations halted
Frequency decreased
Frequency increases prevented
Normal operations (no control)
unit :
°C
unit :
°C
SM830211-07̲PAC-i.indb 13
SM830211-07̲PAC-i.indb 13
2013/08/06 21:55:41
2013/08/06 21:55:41
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...
Page 739: ...201309 ...