Charging Additional Refrigerant
Finishing the Job
(1) With a hex wrench, turn the liquid tube service valve stem counterclockwise to fully open the valve.
(5) Replace the valve caps at both gas and liquid service valves and fasten them securely.
(2) Turn the gas tube service valve stem counterclockwise to fully open the valve.
(3) Loosen the charge hose connected to the gas tube service port (7.94 mm) slightly to release the pressure,
and then remove the hose.
(4) Replace the 7.94 mm flare nut and its bonnet on the gas tube service port and fasten the flare nut securely with
an adjustable wrench or box wrench.
This process is very important to prevent gas from leaking from the system.
* If an additional refrigerant charge has been performed, list the refrigerant tubing length and amount of additional
refrigerant charge on the product label (inside the panel).
CAUTION
To avoid gas from leaking when removing the charge hose, make sure the stem of the gas tube is turned
all the way out (“BACK SEAT”) position.
Charging additional refrigerant (calculated from the liquid tube length as shown in “Amount of additional
refrigerant charge”) using the liquid tube service valve.
Use a balance to measure the refrigerant accurately.
If the additional refrigerant charge amount cannot be charged at once, charge the remaining refrigerant in liquid
form by using the gas tube service valve with the system in Cooling mode at the time of test run.
Lo
Hi
R410A
Manifold valve
Pressure
gauge
Valve
Close
Close
Liquid tube
Gas tube
Outdoor unit
Close
Liquid
Open
Open
Gas tube
Liquid tube
Outdoor unit
Open
SM830211-07̲PAC-i.indb 314
SM830211-07̲PAC-i.indb 314
2013/09/17 22:48:03
2013/09/17 22:48:03
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...
Page 739: ...201309 ...