4-18
4
2) Maximum and Minimum Frequency Control
* There is a case in which the frequency set at maximum and minimum may sometimes decrease in accordance
with ambient temperature and indoor loads.
3) Current Release Control
125PEY1E8
125PEY1E5
60PE1E5
71PE1E8
71PE1E5
125PE1E8
125PE1E5
140PE1E8
140PE1E5
100PE1E8
100PE1E5
PE
PEY
100PEY1E8
100PEY1E5
Maximum Frequency (Hz)
Cooling
Heating
70.0
85.0
15.0
15.0
70.0
85.0
15.0
15.0
55.0
90.0
15.0
15.0
65.0
95.0
15.0
15.0
75.0
100.0
15.0
15.0
70.0
99.0
15.0
15.0
59.0
80.0
15.0
15.0
140PEY1E8
75.0
95.0
15.0
15.0
Minimum Frequency (Hz)
Cooling
Heating
PE
PEY
Is (A)
Cooling
Heating
71PE1E5
14.5
18.0
71PE1E8
—
6.0
7.0
60PE1E5
14.5
18.0
—
—
100PE1E5
24.0
24.0
100PE1E8
8.0
8.5
125PE1E5
26.0
26.0
125PE1E8
8.6
9.5
140PE1E5
27.0
28.0
140PE1E8
9.0
10.5
100PEY1E5
24.0
24.0
100PEY1E8
8.0
8.5
125PEY1E5
27.0
27.0
125PEY1E8
140PEY1E8
9.0
9.5
—
—
—
9.0
9.5
Is (A)
Cooling
Heating
1) Indoor Air Temperature Control
By the control method, not only the thermostat is switched on and off, as explained section “4-12-3”.
Indoor Air Temperature Control ", but also the frequency of the compressor's inverter is controlled in
accordance with
T and fluctuations in indoor air temperature. Inverter frequency is controlled as follows:
· Maximum and Minimum Frequency
When
T is high (not yet reached the temperature set
with the remote controller).
Controlled so that the inverter frequency is increased.
When T is low (approxi1.0 or less in the
cooling mode or approximately -1.0 or more in the
heating mode).
Controlled so that the inverter frequency is decreased
or kept.
The compressor's inverter frequency is controlled in accordance with the model and operation mode.
The maximum and minimum frequencies for each model are shown in the table below.
* There are cases in which frequency is limited with other control functions depending on operational conditions,
so operations are not always carried out in accordance with the maximum frequencies listed below.
The inverter frequency is controlled so that the current value for the inverter compressor is less than the figure
listed in the table below in order to prevent abnormal increases in the inverter circuit located within the outdoor
unit's electrical box.
Current release control with primary current : The limited values are modified in accordance with ambient
temperature.
SM830211-07̲PAC-i.indb 18
SM830211-07̲PAC-i.indb 18
2013/08/06 21:55:42
2013/08/06 21:55:42
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...
Page 739: ...201309 ...