LEAK TEST, EVACUATION AND ADDITIONAL REFRIGERANT CHARGE
pressure in the system rises
water may lead to corrosion of parts in the refrigerant system
operating current rises
cooling (or heating) efficiency drops
moisture in the refrigerant circuit may freeze and block capillary tubing
Perform an air-tightness test for this package A/C. Check that there is no leakage from any of the connections.
Air and moisture in the refrigerant system may have undesirable effects as indicated below.
Therefore, the indoor unit and tubing between the indoor and outdoor unit must be leak tested and evacuated to
remove any noncondensables and moisture from the system.
Check that each tube (both liquid and gas tubes) between the
indoor and outdoor units has been properly connected and all
wiring for the test run has been completed. Remove the valve
caps from both the gas and liquid service valves on the outdoor
unit. Note that both liquid and gas tube service valves on the
outdoor unit are kept closed at this stage.
The refrigerant charge at the time of shipment is only guaranteed sufficient for a tubing length of up to 30* m.
The tubing may exceed this length, up to the maximum permitted length; however, an additional charge is
necessary for the amount that the tubing exceeds 30* m. (No additional refrigerating machine oil is needed.)
* 60, 71 types : 20 m
Manifold gauge
Vacuum pump
Outlet
Inlet
Air Purging with a Vacuum Pump (for Test Run) Preparation
Lo
Hi
Manifold valve
Pressure
gauge
Cylinder
valve
Nitrogen gas cylinder
(In vertical standing
position)
Charge hose
Open
Close
Gas tube
Liquid tube
Outdoor unit
Close
SM830211-07̲PAC-i.indb 312
SM830211-07̲PAC-i.indb 312
2013/09/17 22:48:03
2013/09/17 22:48:03
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...
Page 739: ...201309 ...