Obstructions on the front side and above the unit (Left side, right side and rear side are opened).
A
B
B
A
50 cm
or more
30 cm
or more
In case of multiple installations
Provide a solid base (concrete block, 10 × 40 cm beams
or equal), a minimum of 15 cm above ground level to
reduce humidity and protect the unit against possible water
damage and decreased service life.
Use lug bolts or equal to bolt down unit, reducing vibration
and noise.
Air intake
Air intake
Min. 15 cm
Anchor bolts
(4 pieces)
Air
discharge
Air Discharge Chamber for Top Discharge
Be sure to install the air discharge chamber in the field when:
it is difficult to keep a space of min. 50 cm between the air
discharge outlet and an obstacle.
the air discharge outlet is facing a sidewalk and discharged
hot air annoys passers-by.
Air discharge
Installing the Unit in Heavy Snow Areas
In locations with strong wind, snow-proof ducting should
likewise be fitted and direct exposure to the wind should be
avoided as much as possible.
Countermeasures against snow and wind
In regions with snow and strong wind, the following
problems may occur when the outdoor unit is not provided
with a platform and snow-proof ducting:
a)
b)
c)
d)
The outdoor fan may not run and damage of the unit may
be caused.
There may be no airflow.
The tubing may freeze and burst.
The condenser pressure may drop because of strong wind,
and the indoor unit may freeze.
Without snow-
proof ducting
(Low platform)
With snow-proof
ducting
(High platform)
In regions with significant snowfall, the outdoor unit
should be provided with a platform and snow-proof
duct.
SM830211-07̲PAC-i.indb 301
SM830211-07̲PAC-i.indb 301
2013/09/17 22:48:01
2013/09/17 22:48:01
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...
Page 739: ...201309 ...