H31 HIC Trouble
Error Detection Method
Error Diagnosis
HIC overcurrent due to HIC fault
1.
2.
•
HIC abnormal heat caused by defective HIC or HIC radiation error
•
Signal line is not connected properly or opened between the HIC and the
outdoor CR
board.
•
Measure with an analog tester. (Set to the k ohm range)
•
Measure the board by itself. (Remove wires connected from other parts.)
•
Measure using IPM terminals.
Conforming part resistance value (measure with an analog tester)
•
Excepting the parts of “
value is “0 = short-circuit”.
”, it is acceptable if a small resistance value appears as a reference value unless the
•
HIC board IPM Pass/Fail Tests
It is judged an error if the computer detects an error signal from the HIC.
An error signal is issued by the HIC if abnormal heat occurs inside the HIC or if there is an overcurrent.
However, it is judged an error in the same way if the signal line from the HIC is not connected properly or opened.
1-1
1-2
2-1
3-1
Correct wiring (connector)
Correct wiring (connector)
3-1 : Single-phase model
2-1 : 3-phase model
3-1
Replace wiring
Yes
No
1 Wiring
between
HIC &
outdoor
control
PC board
Yes
Yes
No
No
3-2
4-1
4-2
4-1
Remove foreign matter
Replace the HIC PC board
4-2
Yes
No
3
2
HIC poor
radiation
Yes
No
Everything is normal in the wiring (power cord & signal line)
between the HIC and the outdoor CR board. Check the
wiring one by one with a tester if there is opened and
grounding.
The heat dissipating surface on the back of the HIC is in
good contact with the heat sink (heat dissipating fins) of the
electrical box. Check for looseness in the fastening screws
and the condition of the heat-conducting putty.
1-2
Tighten screw(s),
add putty
Yes
No
3-2
Refer to alarm code P16
Yes
No
Replace the HIC PC board
4 HIC
overcurrent
A good flow of cooling air passes through the heat sink
(heat dissipating fins) of the electrical box.
Check for debris blocking the fins.
The results of the pass/fail tests for the following HIC board
IPM show it to be outside the range of the resistance of a
conforming part.
The inverter compressor was stopped/started more than 10
times and it triggered H31 at a high rate. If alarm code P16
occurs at times, refer to the alarm code P16.
The wiring (power cord and signal line) between the HIC
and the outdoor CR board is connected properly.
The connector CN-PRY1 on the CR PC board is connected
properly (locked). (3-phase only)
Tester terminals
-
Resistance value (ohm)
U
1 k to 5 k
V
1 k to 5 k
W
1 k to 5 k
U
1 k to 5 k
V
1 k to 5 k
W
1 k to 5 k
NU
5 k to 10 k
U
100 k to
V
100 k to
W
100 k to
P
100 k to
U
N
P
+
Tester terminals
+
Resistance value (ohm)
U
N
P
-
U
100 k to
100 k to
V
100 k to
W
100 k to
Check the
outdoor
unit CR
PC board
SM830211-07̲PAC-i.indb 41
SM830211-07̲PAC-i.indb 41
2013/09/07 10:42:20
2013/09/07 10:42:20
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...
Page 739: ...201309 ...