1
1-331
System Control
System control refers to the link wiring connection for control of simultaneous-operation multi systems, group
control, and mainsub remote controller control.
(1) Set the No. 1 wall mounted indoor unit so that it can be operated by the wireless remote controller.
(This is set at the time of shipment.)
On the indoor unit control PCBs, set the No. 2 and following wall mounted units to the sub remote controller.
(Refer to section “Indoor unit remote controller main-sub setting” for K1 type.)
(2) Connect the crossover wiring to the lead wires (white/black) that extend out from the remote controller
connectors of the No. 1 indoor unit and other wall mounted indoor units (as shown in Basic wiring diagram 1).
Connect the crossover wiring to 1 and 2 on the remote control wiring terminal board for units
(4-way, ceilingmounted, etc.) other than the No. 1 indoor unit.
(3) Connect the inter-unit control wiring to 1 and 2 on the No. 1 indoor unit terminal board, and to 1 and 2 on the
outdoor unit terminal board. Also connect the inter-unit control wiring between the indoor units.
(4) When the indoor and outdoor unit power is turned ON, automatic address setting is performed (when there is
only 1 outdoor unit or when the system address is “0”).
Single type and simultaneous-operation multi system
Basic wiring diagram 1
(Wiring procedure)
Simultaneous-operation multi system
Up to 2 (Twin) indoor units can be connected to 1 outdoor unit for operation.
(However, coordinate the outdoor unit capacity and the total capacity of the indoor units.)
(It is not possible to connect individual remote controllers for independent operation.)
Be careful to avoid miswiring when connecting
the wires. (Miswiring will damage the units.)
2
1
L
N
2
1
L
N
L N
1 2
Remote control communication wiring
(Dia. 0.5 to 2 mm
2
)
Total length of wiring 200 m or less
System address (S2)
(Setting at shipment: “0”)
Leakage breaker
Leakage breaker
Outdoor unit
Inter-unit control wiring
Wall
mounted
type
Indoor
unit
No. 1
2P
(white)
Connection to lead wire
(White / Black)
Wireless remote
controller
For group control (wiring locally supplied)
Wall
mounted
type
Indoor
unit
No. 2
L
N
1
2
1
2
1 2
L
N
(Using a wired remote controller with a single-type system)
1.
2.
Wall mounted units do not include a terminal board
for connecting a remote controller.
To connect the remote controller, a remote controller
cord is required.
Leakage breaker
Leakage breaker
Out-
door
unit
Indoor
unit
4P
terminal
board
Wired remote
controller
(Field
supply)
white black
* When using wall mounted units in a simultaneous-operation
multi system, connect the remote control communication
wiring to the remote controller connector (2P) on the main
unit, as shown in the diagram.
N OT E
* If the system address is “0”, automatic address setting is performed when the power is turned ON (in the case
shown in Basic wiring diagram 1).
This requires approximately 4 – 5 minutes (when the outdoor / indoor unit ratio is 1:1 as shown in basic wiring
diagram 1). During automatic address setting, LED 1 and 2 on the outdoor unit control PCB blink alternately.
These LED turn OFF when automatic address setting is completed.
SM830211-07̲PAC-i.indb 331
SM830211-07̲PAC-i.indb 331
2013/09/17 22:48:06
2013/09/17 22:48:06
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...
Page 739: ...201309 ...