1-137
1
Single -Type
1-1. Unit Specifi cations
PE1
6. Low Silhouette Ducted Type S-125PF1E5 / U-125PE1E8
INDOOR
MODEL
S-125PF1E5
OUTDOOR
MODEL
U-125PE1E8
Branch pipe
MODEL
-
PERFORMANCE TEST CONDITION
ISO5151 / EN14825
POWER SUPPLY
ø, Hz
1ø 50Hz
3ø 50Hz
V
220
230
240
380
400
415
Min
Max
C
O
O
L
I
N
G
CAPACITY
kW
12.5
12.5
12.5
3.3
14.0
BTU/h
42700
42700
42700
11300
47800
CURRENT
A
1.48
1.44
1.39
5.52
5.29
5.12
-
-
INPUT POWER
W
215
215
215
3.355k
3.355k
3.355k
-
-
TOTAL W
-
3.570k
3.570k
3.570k
840
4.600k
ANNUAL CONSUMPTION TOTAL W 4
-
-
1785
-
-
-
EER/EER CLASS
TOTAL(W/W) 5/("A"~"G")
-
-
-
3.50
3.50 / A
3.50
3.93
3.04
Erp
6
Pdsign
kW
-
-
-
-
-
-
SEER
(W/W)
-
-
-
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
Class
-
-
-
-
-
-
POWER FACTOR
%
-
-
-
92
92
91
-
-
NOISE INDOOR
(H/M/L)
dB-A
39/35/32
-
Power Level dB
61/57/54
-
NOISE OUTDOOR
(H/L)
dB-A
53/-
Power Level dB
70/-
H
E
A
T
I
N
G
CAPACITY
kW
14.0
14.0
14.0
4.1
16.0
BTU/h
47800
47800
47800
14000
54600
CURRENT
A
1.46
1.42
1.38
5.44
5.26
5.05
-
-
INPUT POWER
W
210
210
210
3.270k
3.270k
3.270k
-
-
TOTAL W
-
3.480k
3.480k
3.480k
900
5.200k
COP/COP CLASS
TOTAL(W/W) 5/("A"~"G")
-
-
-
4.02
4.02 / A
4.02
4.56
3.08
Erp
6
Pdsign
kW
-
-
-
-
-
-
Tbivalen
°C
-
-
-
-
-
-
SCOP
(W/W)
-
-
-
-
-
-
Annual consumption
kWh
-
-
-
-
-
-
Class
-
-
-
-
-
-
POWER FACTOR
%
-
-
-
91
90
90
-
-
NOISE INDOOR
(H/M/L)
dB-A
39/35/32
-
⁄
⁄
Power Level dB
61/57/54
-
NOISE OUTDOOR
(H/L)
dB-A
-
53/-
⁄
⁄
Power Level dB
-
70/-
EXTRA LOW TEMP Total CAPACITY(kW)/INPUT POWER(W)/COP
(Q10.5kW/W5.200kW/COP2.02)
MAX CURRENT(A)/MAX INPUT POWER(W)
1.80/265
1.75/265
1.70/265
10.0/6.200k
10.0/6.500k
10.0/6.750k
⁄
STARTING CURRENT(A)/COMP OUTPUT(W)
-
-
-
5.52/3.0k
5.29/3.0k
5.12/3.0k
⁄
NETWORK IMPEDANCE (
Ω
MAX.)
-
-
FM OUTPUT (W)
200
90×2
⁄
MOISTURE REMOVAL VOLUME
L/h(Pt/h)
7.9
(16.6)
-
External static pressure
Pa
100 (MIN10 - MAX150)
I/D AIR
FLOW
COOL
m
3
/min (ft
3
/min)
34
(1201)
HEAT
m
3
/min (ft
3
/min)
34
(1201)
O/D AIR
FLOW
COOL
m
3
/min (ft
3
/min)
130
(4591)
HEAT
m
3
/min (ft
3
/min)
110
(3885)
REFRIGERANT TYPE, AMOUNT
g
(oz)
R410A 3.40k
(119.9)
/
P
R
O
D
I
M
HEIGHT : H mm(inch)
290 (11-13/32)
1416 (55-3/4)
/
WIDTH : W mm(inch)
1400 (55-1/8)
940 (37-1/32)
/
DEPTH : D mm(inch)
700 (27-9/16)
340 (13-13/32)
/
P
A
C
D
I
M
HEIGHT : H mm
355
1556
/
WIDTH : W mm
1614
1055
/
DEPTH : D mm
850
485
/
MASS
(NET) k
g
(lb)
45 (99)
98
/
(GROSS) k
g
(lb)
54 (119)
108
/
LAYERS LIMIT (actually)
9 (10)
1 (2)
Operation
Condition
Cool O.D(DBT)
18°C ~ 32°C
-15°C ~ 46°C
Heat O.D(DBT)
16°C ~ 30°C
-20°C ~ 24°C
P
I
P
I
N
G
PIPE DIAMETER mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
CONNECT METHOD, STD LENGTH m (ft)
fl
ared type, 5.0(16.4)
fl
ared type, 5.0(16.4)
PIPE LENGTH RANGE m (ft)
5 ~ 75
(16.4 ~ 246.1)
~
~
I/D&O/D HEIGHT DIFFERENCE m (ft)
15 (OD located lower) / 30 (OD located higher)
(49.2/98.4)
ADD GAS AMOUNT
g
/m (oz/ft)
50
(537.6)
PIPE LENGTH FOR ADDITIONAL GAS m (ft)
30
(98.4)
*1
:
In case it is necessary to indicate the air fl ow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:
If the EUROVENT Certifi ed models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230 V shall be used.
*3
:
Network Impedance shall be applicable for EUROPE and CHINA models.
*4
:
The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
:
EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:
SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season,
Other fiche data indicates in an attached sheet.
SM830211-07̲PAC-i.indb 137
SM830211-07̲PAC-i.indb 137
2013/09/17 22:46:19
2013/09/17 22:46:19
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...
Page 739: ...201309 ...