4-4
4
4-2. Heating Standby
In heating mode, the indoor fan speed decreases to prevent cold air discharge from the indoor unit. During this
time, (heating standby) is displayed on the remote controller.
Ԙ
This condition occurs in the following cases.
Thermostat OFF
Defrosting operation
Indoor heat exchanger liquid temperature (E1) < 28˚C and discharge air temperature < 25˚C just after
heating operation started
The fan speed may sometimes increase when this condition continues for 6 minutes.
ԙ
The fan mode increases when the heat exchanger liquid temperature (E1) or discharge air
temperature increases.
The fan mode is selected based on the discharge air temperature and E1 temperature as shown
in the below fi gure. If the E1 temperature and discharge air temperature are different, the higher
temperature is used.
The function of “HH” is identical to the automatic fan speed mode.
Operation
Discharge air
E1
32
Temperature (°C)
30
28
26
20
16
29
27
25
23
17
13
*HH
STOP
L
STOP
STOP
LL
LL
STOP
STOP
LL
LL
L
L
L
L
H
LL L
H
L
H
L
HH
L
H
Set
P
O
T
S
n
a
f
LL
L
H
H
speed
SM830211-07̲PAC-i.indb 4
SM830211-07̲PAC-i.indb 4
2013/08/06 21:55:40
2013/08/06 21:55:40
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...
Page 739: ...201309 ...