6) Cooling Freeze Prevention Control
The following control is performed during cooling operations (including dry mode operation), in accordance
with whichever of the indoor heat exchanger temperatures (E1 or E2) is lower. (See the chart below.)
(1)
(2)
(3)
(4)
(5)
If the temperature remains in the "J" zone (decreasing operation frequency and thermostat OFF zone) for
6 minutes, the operating frequency of the compressor is decreased.
The operation frequency is amended every 30 seconds as long as the temperature is in this zone.
If the temperature is in the "K" zone (operating frequency increase prevention zone), the operating
frequency of the compressor is maintained.
If the temperature is in the "H" zone (operating frequency restriction zone) and the ambient temperature
is less than 32°C, the maximum operating frequency of the compressor is limited in accordance with the
indoor unit fan speed.
If the temperature is in the "I" zone (normal operation zone), normal operations are performed.
If the temperature is continuously in the "J" zone with the compressor's operating frequency reaches "0",
then temperature A, which is temperature for changing from the "J" zone to the "H" zone, is raised from
5°C to 8°C, and operation continues with the thermostat off until the temperature enters the "H" zone.
K (operating frequency increase prevention zone)
TD (discharge)
111
106
100
95
90
7) Discharge Temperature Control
The following control is performed to prevent the discharge temperature from rising abnormally in order to protect
the inverter compressor.
In accordance with the temperature of the discharge sensor TD, such controls are performed as to limiting the
increase of inverter frequency, decreasing it or halting operation of the compressor.
*
°C
If the discharge temperature exceeds 111°C, operations of the compressor are halted and restarted after 3
minutes.
If this start/stop activity is repeated 4 times, the alarm "P03" (abnormal discharge temperature) occurs.
Outdoor unit operation halted
Frequency decreased
Frequency increases prevented
Frequency increased slower than normal
Normal (no control)
SM830211-07̲PAC-i.indb 14
SM830211-07̲PAC-i.indb 14
2013/08/06 21:55:41
2013/08/06 21:55:41
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...
Page 739: ...201309 ...