Tubing Size
(A) Single type
Refrigerant tubing between the indoor and outdoor units should be kept as short as possible.
The lengths of the refrigerant tubes between the indoor and outdoor units are limited by the elevation difference
between the 2 units. During tubing work, try to make both the tubing length (L) and the difference in elevation (H1)
as short as possible.
H1
Single
Main tubing L
Outdoor unit type
U-50PE1E5
U-60PEY1E5
U-71PEY1E5
Maximum allowable
tubing length
40 m
50 m
Charge-less tubing
length
(actual length)
3 – 30 m
3 – 20 m
Additional charge per 1 m
20
g
40
g
(B) Simultaneous operation multi (Twin)
N OT E
Because the indoor units run simultaneously, install them within the same room.
Table 1-1
Contents
m
e
t
I
Symbol
Actual length (m)
Single
Twin
50
60 – 71
single
71
twin
Allowable
tubing
lengths
Maximum
allowable
tubing length
One-way length of tubing
from outdoor unit to the most
distant indoor unit
L
L + 1
L + 2
40
50
40
Maximum
distribution
tubing length
Maximum length following
the first branch point (No. 1
distribution)
–
1, 2
15
Maximum branch tubing
length
Difference between the
maximum length and
minimum length in tubing
following the first branch point
–
1 > 2
1 – 2
10
Maximum difference between lengths of No. 1 distribution
tubing (double twin)
–
–
–
Maximum difference between lengths of No. 2 distribution
tubing (double twin)
–
–
–
–
–
–
–
–
–
–
–
–
–
–
Maximum
allowable
height
difference
Maximum
indoor-
outdoor height
difference
If outdoor unit is higher
H1
30
30
30
If outdoor unit is lower
15
15
15
Maximum height difference between indoor units
H2
0.5
* For connection tubing sizes, refer to Table above.
1
2
H1
H2
Twin
CZ-P155BK1
Main
tubing L
Distribution joint
N OT E
For refrigerant tube branches, use the optional distribution joints.
For cautions on the use of the optional distribution joints, be sure to
refer to the provided instruction sheet.
Also, be careful to install them in the correct direction (orientation).
SM830211-07̲PAC-i.indb 303
SM830211-07̲PAC-i.indb 303
2013/09/17 22:48:01
2013/09/17 22:48:01
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...
Page 739: ...201309 ...