1
1-352
Automatic Address Setting
Basic wiring diagram
(1) Turn on the indoor and outdoor unit power for refrigerant system 1.
Short-circuit the AUTO ADD (CN041) pin.
(2) Next, turn ON the power only at the indoor and outdoor units in a different system. Short-circuit the AUTO ADD
(CN041) pin.
(3) Operation using the remote controller is now possible.
Communication for automatic address setting begins.
<Approximately 4 – 5 minutes are required.>
LED 1 and 2 on the outdoor unit control PCB blink alternately, and turn OFF when address setting is completed.
LED 1 and 2 on the outdoor unit control PCB blink alternately, and turn OFF when address setting is completed.
Repeat the same procedure for each system and complete automatic address setting.
Automatic address setting from the outdoor unit (Y1 type)
Case 1
Link wiring
If the power can be turned ON separately for the indoor and outdoor units in each system:
The indoor unit addresses can be set without running the compressor.
Be sure to use a jig for short-circuiting.
N OT E
A terminal plug (black) is attached to each of the outdoor unit control PCBs.
At only one outdoor unit, leave the terminal plug short-circuit socket on the “Yes” side.
At all the other outdoor units, change the socket (from “Yes” to “No”).
A maximum of 8 indoor units can be connected to 1 remote controller for group control.
↓
↓
↓
↓
↓
↓
3-1
3-2
1-1
1-2
2-1
2-2
Refrigerant
system No. 1
Refrigerant
system No. 2
Refrigerant
system No. 3
(Change setting to “1”)
(Change setting to “2”)
(Change setting to “3”)
Change the
terminal plug
(black) short-
circuit socket
Change the
terminal plug
(black) short-
circuit socket
Inter-unit control
wiring
Remote controller
Remote controller
Inter-unit
control
wiring
No. 1
No. 2
No. 3
Remote control communication
wiring for group control
Remote controller
Indoor unit
Outdoor unit
Terminal board 1, 2
Terminal board 1, 2
System address
rotary switch on the
outdoor unit PCB
SM830211-07̲PAC-i.indb 352
SM830211-07̲PAC-i.indb 352
2013/09/17 22:48:10
2013/09/17 22:48:10
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...
Page 739: ...201309 ...