1
1-324
(Wiring procedure)
Setting the outdoor unit system addresses
(1)
For basic wiring diagram 2 (Set the system addresses: 1, 2, 3...)
Connect the remote controller to the indoor unit remote control wiring terminal board (1, 2).
(Remote control wiring)
(2) Connect the indoor units (U1, U2) and the outdoor units (1, 2). Connect the other outdoor units and indoor
units (with different refrigerant systems) in the same way. (Inter-unit control wiring) Connect the remote control
communication wiring to the indoor units (U1, U2) for each refrigerant system. (Inter-unit control wiring)
(3) Connect the remote control communication wiring (2 wires) from the remote control wiring terminal board
(1, 2) on the indoor unit (unit where the remote controller is connected) to the remote controller terminal board
(1, 2) on the other indoor units. (Remote control communication wiring)
(4) Turn ON both the indoor and outdoor unit power and perform automatic address setting from the remote
controller.
(For the automatic address setting procedure, refer to section “Automatic address setting using the remote
controller”.)
N OT E
* Models with auxiliary heaters cannot be used for crossover wiring of the indoor unit power wires.
(Use a pull box to divide the wiring.)
Be sure to use the indoor unit temperature sensor (body sensor) when using this control. (Status at shipment.)
ON
1
2
Outdoor unit control PCB
DIP switch
System address
System address rotary switch
(Set to “0” at time of shipment)
System address rotary switch
10s 20s
ON
OFF
LED1
LED2
PUMP DOWN(CN042)
EEPROM(IC006)
AUTO ADD(CN041)
System address
Rotary switch(S002)
TERMINAL (CN003)
JP007
System address
DIP switch (S003)
Bottom
side
Up side
HIC
Temperature
sensor
SILENT MODE(CN028,WHT)
RC-P(CN034,RED)
FAN(CN030,WHT)
ROM(CN012,WHT)
OC(CN013,BLU)
EMG(CN014,BRN)
20S(CN09,WHT)
FUSE(30A,F003)
C1(CN021,BLK)
TO(CN022,WHT)
TD,TS(CN023,WHT)
C2(CN020,WHT)
MOV(CN025,WHT)
63PH(CN004,RED)
RC-P(CN032,RED)
System address
10s digit
(2P DIP switch)
System address
1s place
(Rotary switch)
0 Automatic address
(Setting at shipment = “0”)
Both OFF
ON
1
2
“0” setting
1 (If outdoor unit is No. 1)
Both OFF
ON
1
2
“1” setting
2 (If outdoor unit is No. 2)
Both OFF
ON
1
2
“2” setting
11 (If outdoor unit is No. 11)
10s digit ON
ON
1
2
“1” setting
21 (If outdoor unit is No. 21)
20s digit ON
ON
1
2
“1” setting
30 (If outdoor unit is No. 30)
10s digit and 20s
digit ON
ON
1
2
“0” setting
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
System address
No.
SM830211-07̲PAC-i.indb 324
SM830211-07̲PAC-i.indb 324
2013/09/17 22:48:05
2013/09/17 22:48:05
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...
Page 739: ...201309 ...