
5-57
5
Outdoor air intake temperature is high.
4-1
Take measures
4-2
Yes
No
May be caused by poor outdoor unit air flow
(dirty or clogged heat exchanger, blocked discharge port, etc.)
4-2
Correct
4-3
Yes
No
Air short circuit has occurred. This is a phenomenon when
discharged air (exhaust heat) from the outdoor unit is drawn back
into the suction vent.
4-3
Prevent air short
circuit
4-4
Yes
No
Indoor air intake temperature is high.
4-4
Take measures
4-5
Yes
No
Air short circuit has occurred. This is a phenomenon when
discharged air (exhaust heat) from the indoor unit is drawn back
into the suction vent.
4-6
Prevent air short
circuit
5-1
Yes
No
The filter of the indoor unit is clogged.
4-5
Clean the filter
4-6
Yes
No
Possible to operate.
5-1
5-2
6-1
Yes
No
Operating pressure is affected by pressure overload.
5-2
5-3
5-4
Yes
No
Tends to have an overcharge of refrigerant in the system.
5-3
Adjust the amount
of refrigerant
5-4
Yes
No
Tends to operate for a long time turning gas back into liquid.
5-4
Check the operation
of functional parts
5-5
Yes
No
Even though the high pressure saturation temperature is 43°C or
less, the secondary current of the inverter is high.
(The frequency (Hz) ends up dropping due to the current.)
5-6
Replace the
compressor
See what happens.
Yes
No
Tends to have insufficient refrigerant charge in the system.
5-5
Adjust the amount
of refrigerant
5-6
Yes
No
4 Check the
situation
5 Check
operation
Dividing the outdoor EEPROM INV operation time by the number
of times oil was supplied to the system yields 3 hours or less.
6-1
6-2
6-2
Yes
No
The results of HIC board IPM Pass/Fail Tests show the outside the
range of the resistance of a conforming part listed in the next page.
7-1
Replace HIC board
8-1
Yes
No
The compressor is causing a failure in the insulation.
8-1
Replace the
compressor
8-2
Yes
No
The winding resistance of the compressor is abnormal.
Single-phase model
(2.5hp – 3hp)
U-V :
U-W :
V-W :
0.720 ohm
0.726 ohm
0.708 ohm
8-2
Replace the
compressor
9-1
Yes
No
There is a history of H31 in the pre-trip counter of the outdoor
EEPROM alarm history.
6-2
Replace the
compressor and add
oil. However if 6-1
was “no,” it is not
necessary to add oil.
7-1
Yes
No
6 Check
history
7 Check the
HIC boards
8 Check the
compressor
Single-phase model
(4hp – 6hp)
U-V :
U-W :
V-W :
0.490 ohm
0.495 ohm
0.483 ohm
3-phase model
hp: horse power
U-V :
U-W :
V-W :
1.061 ohm
1.079 ohm
1.050 ohm
Standard winding resistance
SM830211-07̲PAC-i.indb 57
SM830211-07̲PAC-i.indb 57
2013/09/07 10:42:32
2013/09/07 10:42:32
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...
Page 739: ...201309 ...