5-25
5
E15 Automatic Address Alarm (The total capacity of indoor units is too low.)
Error Detection Method
It is judged an error the total capacity of indoor units replied by communication is lower than that of outdoor unit.
Connecting indoor unit
The total capacity of indoor units is lower than that of outdoor unit.
•
Some indoor unit(s) are connected but power is not turned on.
•
The CHK pin (CN062/CN071) and/or TEST pin (CN064) of the indoor unit is shorted when its power is turned on.
•
High voltage was applied (over AC200V) in the indoor/outdoor operations line circuit.
•
1.
Is the indoor unit powered off?
1-1
Was the number of indoor units changed after auto address setting
finished?
3-1
Conduct checks prior to auto address setting.
3-2
3-2
3-1
Yes
No
Power on
2-1
Yes
No
Was a high voltage (over AC200V) applied in the indoor/outdoor
operations line circuit?
2-2
2
Is the indoor/outdoor control line opened or shorted?
2-1
Correct the wiring
2-2
Yes
No
Indoor/
outdoor
control line
3 No. of
Indoor
Units
1 Power
Source
Error Diagnosis
2.
3-2
4-1
Yes
No
Disconnect the connector mentioned above on the control PC board
of the indoor unit control PC board and see whether the E15 goes off
after several minutes. (When doing so, if two remote controllers are
being used and the wireless remote controller is the main remote
controller, set the other remote controller as the main.)
Replace wireless remote control parts including wiring.
4-3
4-4
Is the LED blinking on the indoor unit’s control PC board?
4-5
Check all items under the section “Check Prior to Auto Address Setting”.
5-1
The nonvolatile memory (EEPROM) on the indoor unit’s control board is either not installed,
improperly installed or the nonvolatile memory is faulty. Correct this or after replacing the
nonvolatile memory, write model data to it in the remote control detailed settings mode.
4-6
Are the CHK pin and TEST pin on the indoor unit control board
short-circuited?
4-1
Is the wireless remote controller connected to on the indoor unit’s
control PC board?
4-2
4-4
4-5
Yes
No
Remove the short
4-2
Yes
No
4-3
4-5
Yes
No
4 Indoor
unit
control
PC board
5 Outdoor
unit control
PC board
4-6
5-1
Yes
No
For information on the remote control’s detailed settings, refer to the Reference Materials.
•
For information on the procedures for replacing the nonvolatile memory (EEPROM) of the indoor unit, refer to the manual
that is packaged with the indoor unit service board.
•
TEST pin
RC
OPTION
CHK pin
EEPROM
A746803 : Duct Type
A746802 : 4-way Cassette Type
A747711 : Ceiling Type (T2 type)
EEPROM
TEST pin
RC
OPTION
CHK pin
EEPROM
TEST pin
CHK pin
OPTION
RC
名称未設定-1 6
2013/08/06 21:42:53
SM830211-07̲PAC-i.indb 25
SM830211-07̲PAC-i.indb 25
2013/09/07 10:42:07
2013/09/07 10:42:07
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...