1-232
1
Single -Type
1-1. Unit Specifi cations
PEY1
7. Ducted Type S-71PN1E5 / U-71PEY1E5
INDOOR
MODEL
S-71PN1E5
PANEL
MODEL
-
OUTDOOR
MODEL
U-71PEY1E5
Branch pipe
MODEL
-
PERFORMANCE TEST CONDITION
ISO5151 / EN14825
POWER SUPPLY
ø, Hz
1ø 50Hz
1ø 50Hz
V
220
230
240
220
230
240
Min
Max
C
O
O
L
I
N
G
CAPACITY
kW
7.1
7.1
7.1
2.0
7.7
BTU/h
24200
24200
24200
6800
26300
CURRENT
A
1.12
1.08
1.04
12.0
11.5
11.0
-
-
INPUT POWER
W
140
140
140
2.430k
2.430k
2.430k
-
-
TOTAL W
-
2.570k
2.570k
2.570k
325
3.230k
ANNUAL CONSUMPTION TOTAL W 4
-
1285
1285
1285
-
-
EER/EER CLASS
TOTAL(W/W) 5/("A"~"G")
-
-
-
2.76
2.76 / D
2.76
6.15
2.38
Erp
6
Pdsign
kW
-
-
-
-
7.1
-
SEER
(W/W)
-
-
-
-
5.0
-
Annual consumption
kWh
-
-
-
-
496
-
Class
-
-
-
-
B
-
POWER FACTOR
%
-
-
-
92
92
92
-
-
NOISE INDOOR
(H/M/L)
dB-A
43/41/36
-
Power Level dB
60/58/53
-
NOISE OUTDOOR
(H/L)
dB-A
50/-
Power Level dB
70/-
H
E
A
T
I
N
G
CAPACITY
kW
7.1
7.1
7.1
1.8
8.1
BTU/h
24200
24200
24200
6100
27600
CURRENT
A
1.12
1.08
1.04
9.60
9.20
8.90
-
-
INPUT POWER
W
140
140
140
1.940k
1.940k
1.940k
-
-
TOTAL W
-
2.080k
2.080k
2.080k
275
2.780k
COP/COP CLASS
TOTAL(W/W) 5/("A"~"G")
-
-
-
3.41
3.41 / B
3.41
6.55
2.91
Erp
6
Pdsign
kW
-
-
-
-
5.3
-
Tbivalen
°C
-
-
-
-
-7
-
SCOP
(W/W)
-
-
-
-
3.8
-
Annual consumption
kWh
-
-
-
-
1952
-
Class
-
-
-
-
A
-
POWER FACTOR
%
-
-
-
92
92
91
-
-
NOISE INDOOR
(H/M/L)
dB-A
43/41/36
-
⁄
⁄
Power Level dB
60/58/53
-
NOISE OUTDOOR
(H/L)
dB-A
-
52/-
⁄
⁄
Power Level dB
-
70/-
EXTRA LOW TEMP Total CAPACITY(kW)/INPUT POWER(W)/COP
-
MAX CURRENT(A)/MAX INPUT POWER(W)
1.28/0.160k
1.24/0.160k
1.20/0.160k
18.0/3.64k
18.0/3.81k
18.0/3.97k
⁄
STARTING CURRENT(A)/COMP OUTPUT(W)
-
-
-
11.8/2.5k
11.3/2.5k
10.8/2.5k
⁄
NETWORK IMPEDANCE (
Ω
MAX.)
-
-
FM OUTPUT (W)
120
90
⁄
MOISTURE REMOVAL VOLUME
L/h(Pt/h)
4.2
(8.8)
-
External static pressure
Pa
50 (MIN10 ~ MAX80)
I/D AIR
FLOW
COOL
m
3
/min (ft
3
/min)
22
(777)
HEAT
m
3
/min (ft
3
/min)
22
(777)
O/D AIR
FLOW
COOL
m
3
/min (ft
3
/min)
39
(1377)
HEAT
m
3
/min (ft
3
/min)
39
(1377)
REFRIGERANT TYPE, AMOUNT
g
(oz)
R410A 1.70k
(60.0)
/
P
R
O
D
I
M
HEIGHT : H mm(inch)
250
9-27/32
569
22-13/32
/
WIDTH : W mm(inch)
1000 (+100)
39-5/16 (+3-15/16)
790
31-7/64
/
DEPTH : D mm(inch)
650
25-19/32
285
11-7/32
/
P
A
C
D
I
M
HEIGHT : H mm
338
645
/
WIDTH : W mm
1211
921
/
DEPTH : D mm
761
386
/
MASS
(NET) k
g
(lb)
32
42
(93)
/
(GROSS) k
g
(lb)
38
46
(101)
/
LAYERS LIMIT (actually)
6 (7)
4 (5)
Operation
Condition
Cool O.D(DBT)
18°C ~ 32°C
-10°C ~ 43°C
Heat O.D(DBT)
16°C ~ 30°C
-15°C ~ 24°C
P
I
P
I
N
G
PIPE DIAMETER mm (inch)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
(Liquid)ø9.52(3/8) (Gas)ø15.88(5/8)
CONNECT METHOD, STD LENGTH m (ft)
fl
ared type, 5.0(16.4)
fl
ared type, 5.0(16.4)
PIPE LENGTH RANGE m (ft)
5 ~ 50
(16.4 ~ 164.0)
~
~
I/D&O/D HEIGHT DIFFERENCE m (ft)
15 (OD located lower) / 30 (OD located higher)
(49.2/98.4)
ADD GAS AMOUNT
g
/m (oz/ft)
40
(0.430)
PIPE LENGTH FOR ADDITIONAL GAS m (ft)
20
(65.6)
*1
:
In case it is necessary to indicate the air fl ow volume in (l/s), the value in (m
3
/min.) shall be multiplied by 16.7 and rounded down the decimal point.
*2
:
If the EUROVENT Certifi ed models can be operated under the “extra-low” temperature condition, -7°C dry bulb and -8°C wet-bulb temperatures with rated voltage
230 V shall be used.
*3
:
Network Impedance shall be applicable for EUROPE and CHINA models.
*4
:
The annual consumption is calculated by multiplying the input power at 230 V (400 V) by an average of 500 hours per year in cooling mode.
*5
:
EER and COP classification is at 230 V (400 V) only in accordance with EU directive 2002/31/EC.
*6
:
SEER and SCOP classification is at 230V(400V) only in accordance with EN-14825. For heating, SCOP indicates the value of only Average heating season,
Other fiche data indicates in an attached sheet.
SM830211-07̲PAC-i.indb 232
SM830211-07̲PAC-i.indb 232
2013/09/17 22:47:34
2013/09/17 22:47:34
Summary of Contents for U-100PEY1E5
Page 536: ... MEMO 1 526 ...
Page 540: ... MEMO 2 4 ...
Page 549: ...3 9 3 3 1 Indoor Units Ducted Type S 36PN1E5 S 45PN1E5 S 50PN1E5 Electric Wiring Diagram ...
Page 551: ...3 11 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 552: ...3 12 3 3 2 Outdoor Units Single phase U 50PE1E5 ...
Page 553: ...3 13 3 3 2 Outdoor Units Single phase U 60PE1E5 U 71PE1E5 䡵 ...
Page 554: ...3 14 3 3 2 Outdoor Units Single phase U 100PE1E5 U 125PE1E5 U 140PE1E5 䡵 ...
Page 555: ...3 15 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 556: ...3 16 3 3 2 Outdoor Units Single phase U 60PEY1E5 U 71PEY1E5 ...
Page 558: ...3 18 3 3 2 Outdoor Units 3 phase U 71PE1E8 ...
Page 559: ...3 19 3 3 2 Outdoor Units 3 phase U 100PEY1E8 U 125PEY1E8 ...
Page 560: ...3 20 3 3 2 Outdoor Units 3 phase U 100PE1E8 U 125PE1E8 U 140PE1E8 U 140PEY1E8 ...
Page 594: ...4 34 4 HIC PCB A746895 U 60PE1E5 U 71PE1E5 CN VDC U P V W N CN VDC 4WAY Valve CN 20S ...
Page 595: ...4 35 4 HIC PCB continued A746846 U 100PE1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 597: ...4 37 4 HIC PCB A746846 U 100PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 598: ...4 38 4 HIC PCB continued A746847 U 125PEY1E5 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 602: ...4 42 4 HIC PCB A747248 U 100PEY1E8 U 125PEY1E8 CN VDC U V W CN VDC 4WAY Valve CN 20S P NU ...
Page 738: ... MEMO 8 34 ...
Page 739: ...201309 ...